| Notes |
| Date |
Text |
| 2006-06-23 00:00:00 | | | | | | | DENIED | | | | | | 1) NOTE 7(E)ON PREVIOUS REVIEW NOT | | | ADDRESSED, PROVIDE UPDATED NOA THAT | | | BELONGS WITH FL#183 FOR GAF SHINGLES | | | (04-0820.01) | | | | | | 2) NOTE 9 ON PREVIOUS REVIEW NOT | | | ADDRESSED, PROVIDE A NOTE ON DETAIL OF | | | FRAMED BUILDOUTS FOR APPLICATION OF | | | HARDIEPLANK SIDING.SHOW HOW BUILDOUTS | | | ARE ATTACHED, IN REAR TO BLOCK WALL IN | | | FRONT TO SHEATHED GABLE END TRUSS AND | | | HOW THEY ARE CONSTRUCTED (EG.2X4- 16" OC | | | WITH 5/8" PLYWOOD SHEATHING, ETC.) | | | | | | 3) IF LISTING PRODUCT APPROVALS MAKE | | | CORRECTIONS TO LIST AND STATE | | | "REVIEWED AND APPROVED FOR USE" AS WELL | | | AS SIGNITURE | | | | | | ********PROVISO****** | | | SUBMIT ENGINEERED TRUSS DRAWINGS FOR | | | REVIEW PRIOR TO INSTALLATION | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|