Plan Review Notes
Plan Review Notes For Permit 06051230
Permit Number 06051230
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-20 00:00:00** UNSAT **
 ]
 ** PLEASE KNOW, PLANS ARE NOW BEING
 SUBMITTED FOR REVIEW.
 PLEASE SEE COMMENTS BELOW.
  
 1) NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH PANEL SCHEDULE SUBMITTED.
 PLEASE SEE AHU SHOWN ON THE SAME AS
 DRYER.
 PLEASE SEE BATH NOT SHOWING CIRCUIT.
 PLEASE SEE WP GFI. ETC
 PLEASE SEE REDLINED PLANS.
  
 2) NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR A/C CU. 210.63
  
 3) NOTE: PLEASE SEE THAT PANEL SCHEDULE
 PROVIDES LABLELING SPECIFIC TO ROOMS AND
 AREAS IN WHICH THEY FEED.
 IE: BEDRM LTS, HALL LTS ETC.
 408.4
  
 4) NOTE: PLEASE SEE CIRCUITING FOR
 DISHWASHER / DISPOSAL. PLEASE SEE BOTH
 SEEM TO BE FEEDING THE SAME DEVICE ,
 HOWEVER EACH CIRCUIT IS SHOWN AS A SP
 BRKR. PLEASE SEE A SINGLE DEVICE, IF FED
 BY TWO CIRCUITS SHALL BE ON A 2-POLE
 BRKR.
 PLEASE ADJUST.
 210.23,210.4
  
 5) NOTE: PLEASE KNOW, IF ENGINEERING
 FIRM IS BEING DECLARED, PLEASE OBTAIN
 AND PLCE CERITIFICATE OF AUTHORIZATION #
 ON TITLE BLOCKS.
 61G15-23.002, FS 471.023
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  