| Plan Review Notes For Permit 06051230 |
| Permit Number |
06051230 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-20 00:00:00 | ** UNSAT ** | | | ] | | | ** PLEASE KNOW, PLANS ARE NOW BEING | | | SUBMITTED FOR REVIEW. | | | PLEASE SEE COMMENTS BELOW. | | | | | | 1) NOTE: PLEASE CORRELATE ALL CIRCUITING | | | ON PLANS WITH PANEL SCHEDULE SUBMITTED. | | | PLEASE SEE AHU SHOWN ON THE SAME AS | | | DRYER. | | | PLEASE SEE BATH NOT SHOWING CIRCUIT. | | | PLEASE SEE WP GFI. ETC | | | PLEASE SEE REDLINED PLANS. | | | | | | 2) NOTE: PLEASE SEE MISSING GFI RECEPT | | | FOR A/C CU. 210.63 | | | | | | 3) NOTE: PLEASE SEE THAT PANEL SCHEDULE | | | PROVIDES LABLELING SPECIFIC TO ROOMS AND | | | AREAS IN WHICH THEY FEED. | | | IE: BEDRM LTS, HALL LTS ETC. | | | 408.4 | | | | | | 4) NOTE: PLEASE SEE CIRCUITING FOR | | | DISHWASHER / DISPOSAL. PLEASE SEE BOTH | | | SEEM TO BE FEEDING THE SAME DEVICE , | | | HOWEVER EACH CIRCUIT IS SHOWN AS A SP | | | BRKR. PLEASE SEE A SINGLE DEVICE, IF FED | | | BY TWO CIRCUITS SHALL BE ON A 2-POLE | | | BRKR. | | | PLEASE ADJUST. | | | 210.23,210.4 | | | | | | 5) NOTE: PLEASE KNOW, IF ENGINEERING | | | FIRM IS BEING DECLARED, PLEASE OBTAIN | | | AND PLCE CERITIFICATE OF AUTHORIZATION # | | | ON TITLE BLOCKS. | | | 61G15-23.002, FS 471.023 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|