Plan Review Notes
Plan Review Notes For Permit 06051228
Permit Number 06051228
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-12 00:00:00DENIED;
 1.PLANS MUST BE REVIEWED AND APPROVED BY
 THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION, DEVISION OF
 HOTELS AND RESTAURANTS. PLEASE SUBMIT
 APPROVAL PAPER WORK. WEB SITE
 WWW.MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SH
 WW.MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SHT
 W.MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SHTM
 .MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SHTML
 2.PLEASE CONTACT THE WEST PALM BEACH
 UTILITY DEPARTMENT TO DETERMINE IS A
 GREASE TRAP IS REQUIRED AT THIS
 LOCATION. ORD.#3434. WHAT TYPE OF FOOD
 IS TO BE PREPARED?
 3.HOW IS CONDENSATE FOR COOLER TO DRAIN?
 FLOOR DRAIN TO SANITARY OR TO A DRY WELL
 PLEASE SHOW ON PLANS.
 4.BRANCH DRAIN FOR AUTOMATIC CLOTHES
 WASHER IS REQUIRED TO BE 3" PER FBC-2004
 PLUMBING SEC 406.3. A CLEANOUT IS
 REQUIRED AT 48" AFF.
 5.WATER HEATER IS REQUIRED TO HAVE A
 MEANS OF EXPANTION CONTROL SEE
 SEC.607.3. SHOW WERE HEATER PLAN IS TO
 DRAIN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  