| 2006-06-12 00:00:00 | **** UNSAT **** |
| | |
| | PLANS ARE GENERALLY IN GOOD SHAPE, |
| | HOWEVER PLEASE SEE THE FOLLOWING FOR |
| | SOME CORRECTIONS. |
| | |
| | 1) NOTE: PLEASE SEE RISER MENTIONS, FOR |
| | CONDUCTORS TO BE VERIFIED ON SITE. THIS |
| | SHOULD BE DONE AT THIS TIME. |
| | PLEASE VERIFY THE #2 SHOWN FOR THE |
| | EQUIPMENT GROUNDING CONDUCTOR. THIS SIZE |
| | SEEMS MUCH LARGER THAN WHAT WOULD BE |
| | REQUIRED. IF SHOWN AS THIS SIZE, THIS IS |
| | WHAT WILL BE REQUIRED. EXISTING |
| | CONDITION TO BE VERIFIED. |
| | 215.5,250.122,310.16.240.4 |
| | |
| | 2) NOTE: PLEASE SEE FBC |
| | 13-415.1.ABC.1.1,.1.2,.1.3 FOR ALL AREAS |
| | AND LOCATIONS WHICH REQUIRE CONTROLS. |
| | PLEASE SEE BATH RM, SEE WHEN THE EGRESS |
| | PATH IS FROM THE FRONT OF THE STORE A |
| | DEVICE IS REQUIRED EITHER AUTOMATICALLY |
| | OR MANUAL OVER RIDE BY OCCUPANT. PLEASE |
| | SEE A MOTION SENSOR IS SHOWN AT THE REAR |
| | OF THE STORE, HOWEVER PLEASE PROVIDE |
| | SPECS FOR THIS DEVICE AS, THE DISTANCE |
| | AND LOCATION MAY REQUIRE ONE ADDITIONAL |
| | DEVICE EITHER BY MOTION OR TIME SWITCH. |
| | PLEASE ALSO SEE DIPLAY/ ACCENT |
| | LTS(TRACK) LTS SHALL CONTAIN CONTROLS |
| | ALSO. |
| | |
| | 3) NOTE: PLEASE SEE PANEL "A" ON PLANS |
| | INDICATES "RELOCATE". PLEASE SHOW NEW |
| | LOCATION OR IS THIS THE NEW LOCATION.? |
| | 215.5 |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |