| 2006-06-14 00:00:00 | ******** UNSAT ********** |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2) NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 |
| | |
| | 3) NOTE: PLEASE SEE MISSING SEC'S PER |
| | 310.15B6,310.16,240.4,240.6,215.5 |
| | |
| | 4) NOTE: PLEASE SEE FEEDERS ARE NOT |
| | LAREGE ENOUGH FOR 200A SERVICE AS SHOWN |
| | FROM MAIN TO PANEL. |
| | 310.16, 240.4 |
| | |
| | 5) NOTE: PLEASE CORRELATE ALL CIRCUTING |
| | ON PANEL SCHEDULE WITH LOADS ON LOAD |
| | CALCS. |
| | PLEASE SEE RANGE, WATER HEATER, DRYER |
| | ETC. |
| | 215.5 |
| | |
| | 6) NOTE: PLEASE SEE WH IS SHOWNAS 1-15A |
| | BRKR WITH 4500VA LOAD?? |
| | 240.4,310.16,240.6 |
| | |
| | 7) NOTE: PLEASE SEE MANY CIRUITS NOTED |
| | AS ARC FAULT WHICH ARE IN QUESTION?? |
| | WATER HEATER , DRYER ETC?? |
| | PLEASE EXPLAIN. |
| | 215.5 |
| | |
| | 8) NOTE: PLEASE SHOW THE LOCATION ON |
| | PLAN FOR SERVICE LOCATION. |
| | 215.5 |
| | |
| | 9) NOTE: PLEASE SEE MIN CLEARENCES PER |
| | 110.26 FOR AHU AND WH. |
| | |
| | 10) NOTE: PLEASE SEE MIN OCP FOR STOVE |
| | SHOUDL CORRELATE WITH THE KW RATING. |
| | PLEASE SEE LOAD EXCEEDS RATING OF THE |
| | OCP/BREAKER. |
| | 240.4,310.16 ETC |
| | 215.5 |
| | |
| | 11) NOTE: PLEASE SEE PLANS SHALL |
| | INDICATE THE CURRENT CODE IN EFFECT. |
| | 2002 NEC. |
| | FBC ADMIN SECTION AS AOPTED BY THE CITY |
| | OF WEST PALM BEACH 106.2.1 |
| | |
| | 12) NOTE: PLEASE SEE MISSING REQUIRED |
| | LICENSE INFORMATION ON TITLE BLOCKS OF |
| | SAID PLANS. |
| | PLEASE SEE FAC 61G1-16.004, FS481.219. |
| | PLEASE KNOW, THIS IS REQUIRED OF ALL |
| | SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| | COMMENTS IS MADEBY OTHER TRADES. |
| | |
| | 13) NOTE: PLEASE SEE MIN GEC SHALL BE |
| | SIZED PER 250.66. |
| | |
| | 14) NOTE: PLEASE SEE PANEL SCHEDULE |
| | SHOWS TWO BATH RECEPT CIRCUITS?? |
| | PLEASE SEE BOTH ARE SHOWN AS 20A #12, |
| | ONE FOR LT AND ONE FOR RECEPT. |
| | |
| | 15) NOTE: PLEASE SEE MISSING |
| | WASHER/LAUNDRY CIRCUIT PER 210.11C1, |
| | 220.16SHALL BE A MIN OF 1500VA |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |