| 2006-06-07 00:00:00 | PROJECT:PALM BEACH POST |
| | 2751 SOUTH DIXIE HIGHWAY |
| | PERMIT #06051220 |
| | |
| | PLANS EXAMINER: KEN CONRAD |
| | |
| | *****PROVISO****** |
| | |
| | REQUIRE CARBON FIBER |
| | PRODUCT/INSTALLATION |
| | SPECIFICATIONS,BALCONY WATERPROOFING |
| | SPECIFICATIONS AND DETAIL FOR INTERIOR |
| | INFILL WALL FINISH APPLICATIONS. |
| | |
| | |
| | COMMENTS: |
| | |
| | 1)ALL WORK MUST CONFORM TO THE FLORIDA |
| | EXISTING BUILDING CODE. |
| | |
| | 2)THE PROPOSED WORK FOR THE BALCONY |
| | AREAS/SOFFIT FRAMING SHALL COMPLY WITH |
| | LEVEL 1 ALTERATIONS-CHAPTER 5. |
| | |
| | 3)THE PROPOSED WORK FOR THE |
| | REPAIR/ALTERATION OF THE WEST WALL AND |
| | THE STOCK ROOM WINDOWS SHALL COMPLY WITH |
| | LEVEL 2 ALTERATIONS AS DEFINED IN |
| | SECTION 304.1:LEVEL 2 ALTERATIONS |
| | INCLUDE THE RECONFIGURATION OF SPACE, |
| | THE ADDITION OR THE ELIMINATION OF ANY |
| | DOOR OR WINDOW, THE RECONFIGURATION OR |
| | EXTENSION OF ANY SYSTEM, OR THE |
| | INSTALLATION OF ANY ADDITIONAL |
| | EQUIPMENT. |
| | |
| | 4)THE APPROVED PLAN MUST BE REVIEWED BY |
| | THE FIRE DEPARTMENT. |
| | |
| | 5)REQUIRE ENERGY CALCULATIONS AS PER |
| | SECTION 611.1 FOR THE NEW INFILL WALLS |
| | AT THE STOCK ROOM WINDOWS. |
| | |
| | 6)THE EXISTING STOCK ROOM POSSESSES AN |
| | AUTOMATIC SPRINKLER SYSTEM. THIS AREA IS |
| | FULLY SPRINKLERED THROUGH OUT WITH AN |
| | OCCUPANCY LOAD OF 5-6 PEOPLE AND MEETS |
| | THE INTENT OF SECTION 604.2.4.THE |
| | MATERIALS LOCATED WITHIN THE STOCKROOM |
| | ARE PAPER ITEMS, METAL PRINTING PLATES, |
| | AND DEVELOPER FLUIDS WHICH HAVE A RATING |
| | OF 0 IN THE FLAMMABILITY INDEX.THIS WAS |
| | VERIFIED WHEN I VISITED THE PROJECT ON |
| | 6/5/06. |