| Plan Review Notes For Permit 06051212 |
| Permit Number |
06051212 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-19 08:59:52 | ********* PROVSIO ******** | | | | | | | | | 1) NOTE: PLEASE SEE CONFERENCE ROOMS 1201 AND 1203 DO | | | NOT SEEM TO CONTAIN OVER-RIDE DEVICES FOR LIGHTING | | | CONTROLS. PLEASE SEE LIGHTING RELAY SCHEDULE ALSO DOES | | | NOT SEEM TO INDICATE THESE CIRCUITS. | | | | | | 2) NOTE: PLEASE SEE REDLINE E-5 AS COMMENT FOR MINIMUM | | | LEVELS FOR HORN/STROBES IS NOT STAED. THIS HAS NOW | | | BECOME PART OF THE ELECTRICAL PLAN REVIEW PROCESS. | | | PLEASE SEE FBC 200411-4.28., 11-4.28.2, FOR MIN | | | ADUDIBLE LEVELS AND 11-4.28.3(4) FOR MIN LIGHTING | | | CANDELA. | | | | | | ** PLEASE BE SURE TO SHOW THESE AND AND INCLUDE ON | | | PLANS. SUBMIT REVISED PLANS ALONG WITH ANY OTHER | | | REVISIONS BEFORE ANY ROUGHT ELECTRICLA INSPECTION. | | | REVISED STAMPED PLANS MUST BE ON SITE FOR ELECTRICLA | | | INSPECTOR. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PAN REVIEW | | | 561-805-6717 | | 2006-10-18 21:05:33 | IN ELECTRICAL FOR REVIEW, REVIEW IN PROGRESS |
|