| Plan Review Notes For Permit 06051212 |
| Permit Number |
06051212 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-05 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A. FROM PREVIOUS REVIEW: | | | | | | 1. SHT P-1 WATER PIPING SCHEMATIC: SEC | | | 604.9 A WATER HAMMER ARRESTOR SHALL BE | | | INSTALLED WHERE QUICK CLOSING VALVES ARE | | | UTILIZED, AND INSTALLED PER MANUFACTUES | | | SPECIFICATIONS. | | | ****RESPONSE NOTED, BUT THE WATER HAMMER | | | ARRESTOR REQUIRED FOR THE DISH WASHER IS | | | LOCATED AT THE WATER HEATER, AND ON THE | | | COLD WATER LINE. ARRESTOR SHALL BE | | | LOCATED NEAR THE FIXTURE IN AN | | | "EFFECTIVE RANGE" PER PDI-WH 201 AND | | | MANUF. INSTALLATION INSTRUCTIONS. THE | | | ARRESTOR FOR THE ICE MAKER SHALL BE | | | LOCATED NEAR THE REFRIG.. | | | | | | **************NEW COMMENTS************** | | | | | | 1B. THE DATE THAT THE SIGNATURE AND SEAL | | | IS AFFIXED AS PROVIDED HERIN SHALL BE | | | ENTERED ON SAID PLANS OR OTHER DOCUMENTS | | | IMMEDIATELY UNDER THE SIGNATURE OF THE | | | PROFESSIONAL ENGINEER. 61G15-23.002(1) | | | AND FS 471.025. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|