| 2006-08-20 00:00:00 | **** UNSAT 2ND REVIEW ******* |
| | |
| | ** PLEASE SEE SOME NOTE FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES ARE IN NEED OF |
| | ADDRESSING. |
| | |
| | 1) NOTE: OK, AS SCOPE ON PLANS HAS |
| | DECREASED. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: NO, PLEASE SEE THE E-SHEETS |
| | WERE NOTE DATED WHEN SIGNED BY THE |
| | ENGINEER. PLEASE MAKE SURE ALL THE NEW |
| | REVISED SHEETS ARE DATED WHEN SIGNING |
| | AND SEALING SADI DOCUMENTS. FS 471.025, |
| | FAC 61G15-23.002. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE THAT PLANS ARE NOTE DATED BY |
| | THE ARCHITECT OR ENGINEER AS REQUIRED |
| | UNDER FS 481.221, 471.025. |
| | |
| | 5) NOTE: OK/NO, PLEASE SEE NEW ENERGY |
| | CALCUALTIONS WERE SUBMITTED HOWEVER |
| | THESE DO NOT CONTAIN A RAISED SEAL AS |
| | REQUIRED. PLEASE SEE A "RUBBER STAMP" IS |
| | PLACE IN LEIU OF THE REQUIRED RAISED |
| | SEASL. FAC 61G15-23.001 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE CORRECTED ENERGY |
| | CODE CALCULATIONS SHAL BE DESIGNED UNDER |
| | FBC 2004. |
| | PLEASE SEE THEY CURRENTY INDICATE THE |
| | 2001 ICC. |
| | PLEASE BE SURE THEY ARE SIGNED , DATED |
| | AND SEALED BY THE ENGINEER OF RECORD. |
| | PLEASE SEE FBC CHAPTER 13 13-415.1.AB.1, |
| | 13-415.2.ABC.1 |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: OK. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK, SEE NEW NOTES. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: NO, THIS IS UNCLEAR STILL AS |
| | RISER NOW SHOWS A MAIN AHEAD OF THE FPL |
| | METER. PLEASE KNOW, PER FPL GUIDLINES |
| | FOR SERVICES, A MAIN IS REQUIRED ON THE |
| | LOAD SIDE OF METER. PLEASE KNOW, IF |
| | INDEED THIS IS INSTALLED AS SHOWN PLEASE |
| | BE SURE TO INDICATE A "FLOATING |
| | NEUTRAL". |
| | PLEASE SEE NEW NOTES FOR LOAD |
| | CALCUALTIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY RISER, IS THE |
| | "EXISTING TENANT" BEING SHOWN ON THE |
| | RISER ANOTHER TENANT SPACE OR IS THIS |
| | THE EXISTING TENANT RISER FOR THIS |
| | SPACE? |
| | AS SHOWN, THERE SEEMS TO BE AN EXISTING |
| | TENANT AND THIS NEW BUILD OUT IS NOTW |
| | TAPPING THE EXISTING METER AS SHOWN?? |
| | THIS IS NOT CLEAR AT THIS TIME. |
| | 215.5 |
| | |
| | 13) NOTE: NO/UNCLEAR SEE NOTE ABOVE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE EXISTING , OR |
| | NEW METER SIZE AND WHERE THE |
| | DISCONNECTING MEANS FOR SERVICE IS |
| | LOCATED AND THE OCP AND SIZE OF TENANT |
| | SERVICE DISCONNECT. |
| | CURRENTLY THIS IS NOT SHOWING ANY MAIN, |
| | AND A 42 CIRCUIT MLO FOR TENANTS |
| | DISCONNECTING MEANS. |
| | 215.5,240.4,310.16,230.70 ETC |
| | |
| | 14) NOTE: NO, PLEASE SEE ATTACHMENT ONLY |
| | BEING NTOED FOR THE 45K UNIT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE TH ACTUAL |
| | ATTACHMENT FOR THE GROUNDING ELECTRODE |
| | OF THE NEW SEPARATELY DERIVED |
| | TRANSFORMERS. |
| | 250.66, 250.30 |
| | THE NOTE ON PLANS NEEDS TO BE SHOWN. |
| | |
| | 15) NOTE: OK. SEE NEW NOTES. |
| | |
| | |
| | 16) NOTE: OK. |
| | |
| | |
| | ** NEW NOTES** |
| | |
| | 17) NOTE: PLEASE SSUBMIT COMPLETE LOAD |
| | CALCULATIONS FOR THE EXISTING 200A MIAN |
| | AND METER BEING SHOWN. (LOADS FOR "H", |
| | "L" AND "CR. |
| | 220, |
| | FBC 106.1.2 |
| | |
| | 18) NOTE: PLEASE SEE IT ROOM DOES NOT |
| | INDICATE THE TRANSFORMER ON ROOM LAYOUT? |
| | PLEASE SEE RISER AND NOTE MENTIONS THIS |
| | IS A FLR MOUNTED UNIT. |
| | PLEASE SEE 110.26 |
| | |
| | 19) NOTE: PLEASE SEE PANEL "CP" IS BEING |
| | SHOWN AS 125A RATED AND FED FROM "RP" |
| | WHICH IS 150A MCB AND FEED-THRU LUGS. |
| | THEN PANEL "CP" WOULD ALSO BE REQUIRED |
| | TO BE 150A RATED, OR IF USING A TAPPED |
| | CONDUCTOR RULE, TERMINATE IN OCP WHICH |
| | LIMITS THE LOAD. |
| | 240.21, 408.16, 240.3 |
| | THIS WAS SHOWN AS THE SAME ON PREVIOUS |
| | PLANS, HOWEVER WAS NOT COMMENTED ON. |
| | |
| | 20) NOTE: PLEASE SEE THE FOLLOWING AS |
| | THE FIRST COMMENT FROM BUILDING REVIEWER |
| | REQUESTED ALL OLD/VOIDED SHEETS BE |
| | REMOVED, YET PLEASE SEE ALL OLD |
| | ELECTRICAL SHEETS WERE LEFT IN SETS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |