| Plan Review Notes For Permit 06051212 |
| Permit Number |
06051212 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-02 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC 2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | UNSAT | | | | | | 1) SHT P-1WATER PIPING SCHEMATIC: | | | SEC 604.9 A WATER HAMMER ARRESTOR, SHALL | | | BE INSTALLED WHERE QUICK CLOSING VALVES | | | ARE UTILIZED AND INSTALLED PER | | | MANFACTURES SPECIFICATIONS. | | | | | | 2) SPECIFY TYPE OF AIR GAP FITTING FOR | | | DISH WASHER WASTE. | | | | | | 3) PLEASE SEE PLAN REVIEW COMMENTS BY | | | OTHER PLAN REVIEWERS. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|