| Plan Review Notes For Permit 06051212 |
| Permit Number |
06051212 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-22 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS | | | REGARDING FAC REQUIREMENTS FOR TITLE | | | BLOCKS. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. PLEASE NOTE THAT THE WORD | | | CHANGE FROM 'CERTIFICATE' TO 'LICENSE' | | | IS REQUIRED FOR ANY SEALED DRAWINGS | | | SUBMITTED FOR THESE SYSTEMS. | | | | | | 3) FOR SPRINKLER REMODEL, NFPA 13, 2002 | | | EDITION SHALL BE REFERENCED. | | | | | | 4) CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | 5) PLANS ILLUSTRATE ELECTRIC LOCKS AND | | | CARD READERS. WHAT IMPACT WILL THIS | | | ARRANGEMENT HAVE ON REQUIRED EXITING? | | | DOORS SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION SEC. 7.2.1.5. | | | | | | 6) 2A-10B,C RATED FIRE EXTINGUISHERS | | | SHALL BE MOUNTED AT DISTANCES NOT TO | | | EXCEED 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|