| 2006-06-19 00:00:00 | IN ELEC FOR REVIEW. |
| | ********** UNSAT *********** |
| | |
| | 1) NOTE: PLEASE SEE VALUE FOR SCOPE OF |
| | WORK SHALL INCLUDE ALL MATERIALS AND |
| | LABOR (EVEN IF ANY EQUIPMENT IS OWNER |
| | SUPPLIED). |
| | PLEASE SEE UPGRADE , AND SPECIALLY |
| | DESIGNED LIGHTING CONTROL SYSTEMS ETC |
| | SHALL ALOS BE INCLUDED IN VALUE IF SHOWN |
| | ON PLANS. |
| | ALL PERMANANTLY INSTALLED SYSTEMS. |
| | FBC ADMINISTRATIVE SECTION 108.3 AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON ALL TITLE BLOCKS ON PLANS. |
| | PLEASE SEE MISSING ARCHITECTURAL FIRM |
| | CERTIFICATE OF AUTHORIZATION #. |
| | PLEASE SEE MISSING ENGINEERING FIRM CA#. |
| | PLEASE SEE MISSING THE PRINTED NAME AND |
| | PRINTED LICENSE # OF SAID ARCHITECT. |
| | PLEASE SEE ALL OF THE ABOVE IS REQUIRED |
| | PER FLORIDA ADMINISTRATIVE CODES |
| | 61G1-16.004, 61G15-23.002, FLORIDA |
| | STATUES 481.219, AND FS471.023 |
| | ** THIS IS REQUIRED OF ALL TRADES AND |
| | FOR ALL SHEET WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.001 WHICH |
| | PASSED A RULING IN FEB 04 WHICH REQUIRED |
| | ALL ENGINEER'S SEALS TO CONTAIN THE |
| | WORDING OF "LICENSE" IN SEAL. PLEASE SEE |
| | THAT ALL SEALS WITH THE WORDING OF |
| | "CERTIFICATE" ARE NOT LONGER ACCEPTABLE. |
| | |
| | 4) NOTE: PLEASE SEE THAT PLANS ARE NOT |
| | DATED BY THE ARCHITECT OR ENGINEER AS |
| | REQUIRED UNDER FS 481.221 AND 471.025 |
| | |
| | 5) NOTE: PLEASE SEE CORRECTED ENERGY |
| | CODE CALCULATIONS SHAL BE DESIGNED UNDER |
| | FBC 2004. |
| | PLEASE SEE THEY CURRENTY INDICATE THE |
| | 2001 ICC. |
| | PLEASE BE SURE THEY ARE SIGNED , DATED |
| | AND SEALED BY THE ENGINEER OF RECORD. |
| | PLEASE SEE FBC CHAPTER 13 13-415.1.AB.1, |
| | 13-415.2.ABC.1 |
| | |
| | 6) NOTE: PLEASE BE SURE PLANS INCLUDIGN |
| | ELECTRICAL REFLECT THE CURRNT CODE IN |
| | EFFECT FOR DESIGN. |
| | PLEASE SEE PLANS SHOULD INCLUDE THE |
| | FOLLOWING AT A MIN. |
| | 2002 NFPA-70, (2005 SHOWN), 2003 |
| | NFPA-101, NFPA-72 2002, NFPA-75 2003. |
| | |
| | 7) NOTE: PLEASE CLARIFY LIGHTING |
| | CONTROLS FOR ALL ROOMS AS SOME COULD NOT |
| | BE LOCATED FOR THE OVER RIDE DEVICES AS |
| | REQUIRED. |
| | FBC 13-415.1.ABC.1.1, .1.2 ETC. |
| | 1205,1202,1203,1201 |
| | ** PLEASE SPECIFY TIME LIMITS ON |
| | DEVICES. CAN BE A "TYPICAL" NOT FOR NO |
| | MORE THAN 30 MINS FOR OS TYOE DEVICES |
| | AND 4HRS FOR TIMED TYPE DEVICES. |
| | ** PLEASE SEE A OSZ2 DEVICE IS SHOWN ON |
| | PLANS, HOWEVER COULD NOT LOCATED THIS ON |
| | LEGEND? |
| | |
| | 8) NOTE:PLEASE SEE FIRE REVIEW |
| | COMMENTS AS TYPE OF "ELEC LOCK" FOR |
| | ACCESS CONTROLS NEED TO BE CLARIFIED. |
| | PLEASE SEE THAT IN THE EVENT OF POWER |
| | FAILURE, EGREES SHALL NOT IMPEDED. |
| | |
| | 9) NOTE: PLEASE SEE THAT PLANS CLEARLY |
| | INDICATE THE FLR AND SUITE NUMBER IN |
| | TITLE BLOCK. |
| | FAC 61G1-16.004 |
| | |
| | 10) NOTE: PLEASE KNOW, AN "ALTERNATE" |
| | SYSTEM IS BEING SHOWN FOR THE IT ROOM. |
| | PLEASE KNOW, IF THIS SYSTEM IS BEING |
| | PROPOSED THEN IT SHOULD BE ON PLANS, IF |
| | NOT THIS SHOULD BE REMOVED. IF THIS |
| | SYSTEM IS GOING TO BE INSTALLED, PLEASE |
| | PROVIDE ALL MANUFACTURES SPCES/CUT |
| | SHEETS INDICATE A LISTING FROM A NRTL. |
| | 215.5 |
| | |
| | 11) NOTE: PLEASE CLARIFY ROOM BEING |
| | INDICATE AS AN "IT" ROOM ON PLANS WHICH |
| | SHALL MEET NFPA-75 AND NEC 645. |
| | PLEASE CLARIFY IF THERE IS A RAISED |
| | FLOOR? IF SO, PLEASE INDICATE THE |
| | REQUIRMENTS/ SD UNDER FLR. |
| | 8.2 |
| | |
| | 12) NOTE: PLEASE CLARIFY RISER, IS THE |
| | "EXISTING TENANT" BEING SHOWN ON THE |
| | RISER ANOTHER TENANT SPACE OR IS THIS |
| | THE EXISTING TENANT RISER FOR THIS |
| | SPACE? |
| | AS SHOWN, THERE SEEMS TO BE AN EXISTING |
| | TENANT AND THIS NEW BUILD OUT IS NOTW |
| | TAPPING THE EXISTING METER AS SHOWN?? |
| | THIS IS NOT CLEAR AT THIS TIME. |
| | 215.5 |
| | |
| | 13) NOTE: PLEASE PROVIDE EXISTING , OR |
| | NEW METER SIZE AND WHERE THE |
| | DISCONNECTING MEANS FOR SERVICE IS |
| | LOCATED AND THE OCP AND SIZE OF TENANT |
| | SERVICE DISCONNECT. |
| | CURRENTLY THIS IS NOT SHOWING ANY MAIN, |
| | AND A 42 CIRCUIT MLO FOR TENANTS |
| | DISCONNECTING MEANS. |
| | 215.5,240.4,310.16,230.70 ETC |
| | |
| | 14) NOTE: PLEASE INDICATE TH ACTUAL |
| | ATTACHMENT FOR THE GROUNDING ELECTRODE |
| | OF THE NEW SEPARATELY DERIVED |
| | TRANSFORMERS. |
| | 250.66, 250.30 |
| | THE NOTE ON PLANS NEEDS TO BE SHOWN. |
| | |
| | 15) NOTE: PLEASE SEE MININUM CLEARENCES |
| | FOR TRANSFORMER AND PANELS DO NOT MEET |
| | 110.26, 450.13,450.9 ETC |
| | PLEASE SEE PLANS MENTIONS THESE TO BE |
| | FLR MOUNTED WHICH WOULD PLACE THEM |
| | DIRECTLY INFRONT OF PANEL(S). |
| | |
| | 16) NOTE: PLEASE VERIFY LOAD |
| | CALCULATIONS WHICH SHOULD INDICATE ALL |
| | CONTINOUS LOADS AT 125%. |
| | PLEASE SEE THE DEMAND IS SHOWN AS 1.25 |
| | ON PANELS, BUT NOT ON MAIN PANEL AND THE |
| | CONTINUOUS LOADS DO NOT NOT SEEM TO HAVE |
| | BEEN CARRIED OVER. |
| | 215.3,230.42 |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT |
| | ELECTRICAL PLANS AND DESIGN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |