| 2006-06-20 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06051212 |
| | ADD: 777 S FLAGLER# 1200 |
| | CONT: HEDRICK BROTHERS |
| | TEL: (561)718-8341 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) SEE ELECTRICAL COMMENTS 2-5 ON |
| | LICENSING LAWS FL S. S. 471/ 481 FOR |
| | ENGINGEERS & ARCHITECTS. |
| | |
| | 3) SHEET A0.03 |
| | 3A) PROJECT CODE DATA IS MISSING MINIMUM |
| | BUILDING TYPE SEE TABLE 503. |
| | |
| | 3B) APPLICABLE CODE DATA LIST THE 2004 |
| | FBC BUT NO MENTION TO THE 2004 FBC |
| | EXISTING BUILDING CODE PROVIDE WHAT |
| | LEVEL OF RENOVATION IS TO TAKE PLACE. |
| | |
| | 4) SHEET A7.00 DETAILS 7 & 8 BOTH REFER |
| | TO DETAIL 1/ OF SHEET 9.00 MISSING? |
| | |
| | 5) BOTH OF THE DETAILS MENTIONED ABOVE |
| | INDICATE THE USE OF WOOD PANELS, PROVIDE |
| | ADDITIONAL INFORMATION. WOOD PANEL |
| | FINISHES PROVIDE DOCUMENTATION TO BEING |
| | TESTED TO ASTM E 84 OR NFPA 286. |
| | 803.1/ 803.2. |
| | |
| | 6) DETAIL# 5/ A8.20 INDICATES THE USE OF |
| | |
| | 3/4" PANELING WITHOUT SOLID BACKING. |
| | SEE 803.4.2,803.4.2 SET-OUT |
| | CONSTRUCTION. |
| | WHERE WALLS AND CEILINGS ARE REQUIRED TO |
| | BE OF FIRE-RESISTANCE-RATED OR |
| | NONCOMBUSTIBLE CONSTRUCTION AND WALLS |
| | ARE SET OUT OR CEILINGS ARE DROPPED |
| | DISTANCES GREATER THAN SPECIFIED IN |
| | SECTION 803.4.1 , CLASS A FINISH |
| | MATERIALS SHALL BE USED EXCEPT WHERE |
| | INTERIOR FINISH MATERIALS ARE PROTECTED |
| | ON BOTH SIDES BY AN AUTOMATIC SPRINKLER |
| | SYSTEM OR ATTACHED TO NONCOMBUSTIBLE |
| | BACKING OR FURRING STRIPS INSTALLED AS |
| | SPECIFIED IN SECTION 803.4.1 . THE |
| | HANGERS AND ASSEMBLY MEMBERS OF SUCH |
| | DROPPED CEILINGS THAT ARE BELOW THE MAIN |
| | CEILING LINE SHALL BE OF NONCOMBUSTIBLE |
| | MATERIALS, EXCEPT THAT IN TYPE III AND V |
| | CONSTRUCTION, FIRE-RETARDANT-TREATED |
| | WOOD SHALL BE PERMITTED. THE |
| | CONSTRUCTION OF EACH SET-OUT WALL SHALL |
| | BE OF FIRE-RESISTANCE-RATED CONSTRUCTION |
| | AS REQUIRED ELSEWHERE IN THIS CODE. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |