| Plan Review Notes For Permit 06051169 |
| Permit Number |
06051169 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-02 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1}PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 2} NOTE THAT THE SIGNATURE OF THE EN- | | | GINEER IS REQUIRED ON HIS/HER SEAL PER | | | 471.025 FS & 61G15-23.002 FLORIDA | | | ADMINISTRATIVE CODE INITIALS ARE NOT | | | ACCEPTABLE PER F.B.P.E. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH, FL | | | 561/805-6718 | | | [email protected] | | | | | | | | | |
|