| Plan Review Notes For Permit 06051158 |
| Permit Number |
06051158 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-10 00:00:00 | ***APPROVED*** | | | | | | 1) PLEASE SEE FIRE SPRINKLER NOTE (1) ON | | | M-2 REFERENCING NFPA 13R, RESIDENTIAL UP | | | TO AND INCLUDING (4) STORIES IS | | | INCORRECT. FIRE SPRINKLER WORK SHALL | | | COMPLY WITH NFPA 13, 2002 EDITION. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|