| Plan Review Notes For Permit 06051158 |
| Permit Number |
06051158 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-07 00:00:00 | | | | | | | | | | NONCOMPLIANT | | | | | | THESE COMMENTS ARE THE SAME AS THE | | | PREVIOUS REVIEW. | | | | | | 1} PROVIDE THE NUMBERS OF THE POWER POLE | | | THE CIRCUITS ARE SERVING ON THE PANEL | | | SCHEDULE, AND AT THE POLES. | | | | | | 3} INDICATE CIRCUIT NUMBERS AT LIGHT | | | HOME RUN LOCATIONS. | | | | | | 4} SHOW COMPLIANCE WITH 13.415 FBC | | | ENERGY CODE. | | | | | | COMMENT #4 WAS ADDRESSED IN A NOTE ONLY. | | | THE COMMENT NEEDS TO BE ADDRESSED | | | DIAGRAMATICALLY. SHOW LOCATIONS OF | | | DEVICES AND TIMERS, INDICATE SYSTEM | | | USED. | | | | | | THE TITLE BLOCK OF THE ARCHITECTURAL | | | FIRM MUST CONTAIN THE CERTIFICATE OF | | | AUTHORIZATION NUMBER REQUIRED BY THE | | | STATE PER 61G1-16.004(2). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|