2006-06-09 00:00:00 
  
 NONCOMPLIANT
  
 1} PROVIDE THE NUMBERS OF THE POWER POLE
 THE CIRCUITS ARE SERVING ON THE PANEL
 SCHEDULE, AND AT THE POLES.
  
 2} PROVIDE A LOAD CALCULATION FOR PANEL
 "10LA". 215.5 NEC.
  
 3} INDICATE CIRCUIT NUMBERS AT LIGHT
 HOME RUN LOCATIONS.
  
 4} SHOW COMPLIANCE WITH 13.415 FBC
 ENERGY CODE.
  