| Plan Review Notes For Permit 06051158 |
| Permit Number |
06051158 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-09 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | 1} PROVIDE THE NUMBERS OF THE POWER POLE | | | THE CIRCUITS ARE SERVING ON THE PANEL | | | SCHEDULE, AND AT THE POLES. | | | | | | 2} PROVIDE A LOAD CALCULATION FOR PANEL | | | "10LA". 215.5 NEC. | | | | | | 3} INDICATE CIRCUIT NUMBERS AT LIGHT | | | HOME RUN LOCATIONS. | | | | | | 4} SHOW COMPLIANCE WITH 13.415 FBC | | | ENERGY CODE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|