| 2007-03-01 09:17:04 | *** UNSAT 3RD REVIEW *** |
| | |
| | ** PLEASE SEE SCOPE OF WORK AND PLANS HAS NOW |
| | COMPLETELY CHANGED. PLEASE SEE COMMENTS. |
| | |
| | 1) NOTE: PLEASE SEE PLANS NOW CALL FOR FAMILY ROOM AS |
| | EXISTING WHEREAS THE PREVIOUS TWO SETS OF PLANS |
| | SUBMITTED INDICATED THIS AREA AS A NEW PROPOSED |
| | ADDITION. PLEASE CLARIFY THIS AS REVIEW IS NOW CONFUSED |
| | OVER SEPARATE PLANS FOR NEW AND EXISTING. |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE FBC R313 FOR NEW SMOKE ALARMS |
| | NEEDED. PLEASE ALSO SEE NOTE BELOW. |
| | ** |
| | PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| | SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| | INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| | ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| | THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| | OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| | ALARMS. |
| | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | |
| | 3) NOTE: PLEASE SEE RISER AND PANEL AND NOTES FOR PANEL |
| | DO NOT CORRELATE. SHOWS 200AMP MAIN BREAKER ON A 150AMP |
| | PANEL AND ALSO SHOWS A 150AMP RATED MAIN?? |
| | 106.1.2. |
| | NEC 230.70, 310.16, 240.4 ETC |
| | |
| | 4) NOTE: PLEASE SEE THE SEALS ON PLANS ARE NOT CLEAR |
| | AND VISIBLE ON PLANS AS REQUIRED PER FAC 61G15-23.001, |
| | .002 AND FS 471.025. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 5) NOTE: PLEASE SEE MISSING RECEPTACLE(S) PER 210.52, |
| | REDLINED IN ADDITION. |
| | |
| | 6) NOTE: PLEASE SEE MISSING COUNTER SPACE GFI PER |
| | 210.8A6. |
| | |
| | 7) NOTE: PLEASE SEE PLANS INDICATE A NEW STOVE, YET NO |
| | RECEPTACLE OUTLET IS BEING SHOWN FOR THIS? PLEASE ALSO |
| | SEE THAT THE REFRIGERATOR IS BEING SHOWN THE SAME WAY. |
| | PANEL SCHEDULE INDICATES BOTH OF THESE. |
| | PLEASE CORRELATE. |
| | 106.1.2. |
| | |
| | 8) NOTE:PLEASE SEE DISHWASHER AND DISPOSAL BEING |
| | SHOWN ON THE SAME SINGLE POLE CIRCUIT WHICH WILL PLACE |
| | LOAD ON THIS CIRCUIT WHICH EXCEEDS THAT OF THE RATING |
| | OF SAID BREAKER. |
| | PLEASE SEE 210.4. |
| | PLEASE SEE 240, 310.16, 422ETC |
| | PLEASE SEE FBC 106.3.5.4 |
| | |
| | 9) NOTE: PLEASE SEE PANEL SCHEDULE WHICH IS MISSING THE |
| | TWO REQUIRED SMALL APPLIANCE CIRCUITS AS SHOWN IN LOAD |
| | CALCULATIONS. |
| | 210.52B1, 210.11C1, 220.16 |
| | |
| | 10) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION FOR |
| | THE AHU IS BEING SHOWN IS HIGH FOR A UNIT WHICH IS |
| | BEING SHOWN AS 7.5KW ON LOAD CALCULATIONS. PLEASE SEE |
| | THE MECHANICAL PLANS INDICATE THIS UNIT AS 10KW. IF |
| | INDEED THIS IS THE CASE, THEN REVISE THE LOAD |
| | CALCULATIONS AND NOT THE OVER CURRENT PROTECTION OF THE |
| | BREAKER AS SHOWN ON PANEL SCHEDULE. |
| | 240.4, 310.16 ETC |
| | PLEASE SEE 220.31B FOR LOAD CALCULATIONS FOR ADDITIONS |
| | TO EXISTING DWELLINGS. |
| | PLEASE SEE THAT PLANS SEEM TO BE INDICATING A NEW CU, |
| | OR IS THIS RELOCATED. PLEASE SEE THE CLEARANCE REQUIRED |
| | FOR A/C EQUIPMENT ON THE ELECTRICAL PLANS DOES NOT SEEM |
| | TO BE MET FOR MINIMUM REQUIRED FOR CU EQUIPMENT. PLEASE |
| | SEE THE MECHANICAL PLANS ARE DIFFERENT. |
| | 110.26 AND SEE MECHANICAL CODE FOR THEIR MINIMUM |
| | REQUIRED. |
| | |
| | 11) NOTE: PLEASE SEE MISSING GFI FOR NEW CU. 210.63, |
| | 210.8A2 |
| | |
| | 12) NOTE: PLEASE SEE OTHER CIRCUITS BEING SHOWN ON |
| | PANEL SCHEDULE WHICH ARE SHOWN AS BLANK OR OTHER 2-POLE |
| | BREAKERS AS SPARES?? |
| | PLEASE CLARIFY. |
| | PLEASE INDICATE THE CIRCUITS FOR NEW WIRING AND ANY |
| | EXISTING AS SUCH. |
| | 408.6, 240.4, 310.16, |
| | FBC 106.3.5.4 |
| | |
| | 13) NOTE: ** PLEASE KNOW THAT ONE SET OF EACH SET OF |
| | PLANS WILL BE RETAINED AND PLACED WITH PREVIOUS HELD |
| | PLANS FOR THE SAME DESIGNER OF RECORD AND FORWARDED TO |
| | THE STATE OF FLORIDA, AND FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS. PLEASE SEE FS 471.025(3) |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |