| Plan Review Notes For Permit 06051149 |
| Permit Number |
06051149 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-03-01 11:54:25 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) THE MECHANICAL PLANS NEED THE PREPARER'S SIGNATURE | | | ON THEM. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | 3) THE MECHANICAL PLANS ARE SHOWING A 4" SUPPLY AIR | | | DUCT TO THE MASTER BEDROOM WITH 196 CFM'S, THAT WOULD | | | BE AT A VELOCITY OF 2250 FPM. MANUAL J CALCULATIONS | | | STATE MAXIMUM VELOCITY TO BE 900 FPM, PLEASE CORRECT. | | | | | | 4) MECHANICAL PLANS SHOW A 10" SUPPLY AIR DUCT TO THE | | | MIXING BOX FOR THE MASTER SUITE, THIS WOULD REQUIRE A | | | 14" RETURN AIR TRANSFER DUCT. PLANS DO NOT STATE IF THE | | | RETURN AIR DUCT IS A TRANSFER DUCT OR DIRECT DUCTED TO | | | THE AHU, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|