| Plan Review Notes For Permit 06051135 |
| Permit Number |
06051135 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-31 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- ENGLERT SERIES 1300 METAL PANELS | | | (DADE COUNTY NOA #03-0108.03): | | | A) MAXIMUM DESIGN PRESSURES FOR THIS | | | SYSTEM IS -60PSF. DESIGN PRESSURES FOR | | | CORNER AND PERIMETER ZONES ARE HIGHER. | | | SEE TABLE 1609.6B FBC 2004. NEED TO | | | PROVIDE CALCULATIONS FOR INCREASED | | | DESIGN PRESSURES AT THESE ZONES. ALL | | | CALCULATIONS TO BE PERFORMED SIGNED AND | | | SEALED BY ANY ONE OF THE PROFESSIONALS | | | LISTED IN SYSTEM LIMITATION NUMBER 1. | | | SEE PAGE 5 OF 6. | | | B) CLEARLY IDENTIFY APPROVED ASSEMBLY | | | TO BE INSTALLED. SEE ATTACHED COPY OF | | | CITY POLICY FOR RE-ROOFING PERMITS AND | | | INFORMATION REQUIRED TO BE SUBMITTED. | | | C) SPECIFY MEAN ROOF HEIGHT. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|