| Plan Review Notes For Permit 06051107 |
| Permit Number |
06051107 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-26 00:00:00 | | | | | | | DENIED | | | | | | 1) PREVIOUS APPLICATION HAS HARDWOOD | | | FLOOR AND THIS APPLICATION DOES NOT, BUT | | | HAS SPRAY TEXTURE. PLEASE PROVIDE A | | | COMPLETE SCOPE OF WORK | | | | | | 2) THE USE OF COMBUSTIBLE MATERIALS IN | | | TYPE 1 AND 2 CONSTRUCTION SHALL MEET THE | | | REQUIREMENTS OF 603.1 FBC (FIRE | | | RETARDANT TREATED WOOD) PLEASE STATE ON | | | DRAWINGS | | | | | | 3) DEPENDING ON SCOPE OF WORK THE | | | CLAIMED VALUATION ON THE PERMIT | | | APPLICATION MAY BE LOW. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT | | | COST EXCLUDING LAND VALUE. OUR VALUATION | | | REFERENCE IS ICC (BVD), MARSHALL-SWIFT | | | AND MEANS COST ANALYSIS SERVICES PER | | | 108.3 FBC* | | | | | | 4) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|