| Plan Review Notes For Permit 06051096 |
| Permit Number |
06051096 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-20 00:00:00 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} ADD RECEPTACLES PER 210.52 AND | | | LIGHTING PER 210.70. ONE BEDROOM HAS NO | | | LIGHTING OUTLETS OR SWITCHES. | | | | | | 2} A RECEPTACLE IS REQUIRED IN THE HALL | | | PER 210.52(H). THIS WAS REDLINED ON PLAN | | | , PREVIOUS REVIEW. | | | | | | 3} REMOVE OLD SHEETS AND REPLACE WITH A | | | NEW, CORRECTED SET. ONE SET SUBMITTED | | | FOR THIS REVIEW WAS THE REDLINED SET. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | |
|