| Plan Review Notes For Permit 06051096 |
| Permit Number |
06051096 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-12 00:00:00 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} ADD RECEPTACLES PER 210.52 AND | | | LIGHTING PER 210.70. ONE BEDROOM HAS | | | NONE. | | | | | | 2} SMOKE DETECTORS ARE REQUIRED INSIDE | | | AND OUT OF BEDROOMS, SHOW ON PLAN, | | | R313.1 FBC. | | | | | | 3} THERE IS NO BATH CIRCUIT ON THE PANEL | | | SCHEDULE, SEE 210.11(C)(3). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | CONSTRUCTION SERVICES DEPARTMENT | | | 561) 805-6718 |
|