2006-06-22 00:00:00********** UNSAT ************
  
 1) NOTE: PLEASE SEE ZONING COMMENTS,A ND
 PLEASE KNOW, THIS GENERARTOR IS LOCATED
 IN A FLOOD ZONE "A" AND WILL REQUIRED
 ELEVATION OF EXSITING BFE AND NEW
 EQUIPMENT ELEVATION.
  
 **PLEASE KNOW, AN ELEVATION CERTIFICATE
 WILL BE REQUIRED BEFORE FINAL
 INSPECTION.
  
 2) NOTE: PLEASE PROVIDE SIZE OF NEW
 METER CAN SHOWN.
 215.5
  
 3) NOTE: PLEASE COMPLETE GROUNDING
 ELECTRODE AND GROUNDING ELECTRODE RISER.
  
 250.50,250.66
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE ALSO INDICATE THE RATING FOR ATS.
  
 5) NOTE: PLEASE RE-CONFIGURE A/C LOADS
 WHICH ARE SHOWN AT 40%??
 PLEASE KNOW, A/C LOADS SHALL BE BASED ON
 HEAT LOADS UNLESS, AUTOMATIC LOAD
 SHEDDING IS PROVIDED. EITHER REFIGURE
 LOAD CALCS OR PROVIDE DETAIL FOR THE
 LOAD SHEDDING.
 702.5,,220,225.35 ETC.
  
 6) NOTE: PLEASE SEE THAT THE RESPONSIBLE
 LICENSE CONTRACTOR SHALL PRINT NAME AND
 SIGN PLANS.
 FBC 106.2.1, 106.3.2.1 ADMIN SECT AS
 ADOPTED BY THE CITY OF WEST PALM BEACH
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved