| 2006-06-22 00:00:00 | ********** UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE ZONING COMMENTS,A ND |
| | PLEASE KNOW, THIS GENERARTOR IS LOCATED |
| | IN A FLOOD ZONE "A" AND WILL REQUIRED |
| | ELEVATION OF EXSITING BFE AND NEW |
| | EQUIPMENT ELEVATION. |
| | |
| | **PLEASE KNOW, AN ELEVATION CERTIFICATE |
| | WILL BE REQUIRED BEFORE FINAL |
| | INSPECTION. |
| | |
| | 2) NOTE: PLEASE PROVIDE SIZE OF NEW |
| | METER CAN SHOWN. |
| | 215.5 |
| | |
| | 3) NOTE: PLEASE COMPLETE GROUNDING |
| | ELECTRODE AND GROUNDING ELECTRODE RISER. |
| | |
| | 250.50,250.66 |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE ALSO INDICATE THE RATING FOR ATS. |
| | |
| | 5) NOTE: PLEASE RE-CONFIGURE A/C LOADS |
| | WHICH ARE SHOWN AT 40%?? |
| | PLEASE KNOW, A/C LOADS SHALL BE BASED ON |
| | HEAT LOADS UNLESS, AUTOMATIC LOAD |
| | SHEDDING IS PROVIDED. EITHER REFIGURE |
| | LOAD CALCS OR PROVIDE DETAIL FOR THE |
| | LOAD SHEDDING. |
| | 702.5,,220,225.35 ETC. |
| | |
| | 6) NOTE: PLEASE SEE THAT THE RESPONSIBLE |
| | LICENSE CONTRACTOR SHALL PRINT NAME AND |
| | SIGN PLANS. |
| | FBC 106.2.1, 106.3.2.1 ADMIN SECT AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |