| Date |
Text |
| 2006-06-22 00:00:00 | ********** UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE SITE SURVEY WHICH |
| | WILL REQUIRE ALL SETBACKS AND DIMENSIONS |
| | FROM DWELLING AND PROPERTY LINES. PLEASE |
| | SEE THAT THE CLEARENCS OF THE GEN CAN |
| | NOT BE VERIFIED AT THIS TIME. |
| | 215.5 |
| | |
| | 2) NOTE: PLEASE PROVIDE A SERVICE |
| | ENTRANCE RATED ATS WHICH DISCONNECTS |
| | POWER FROM FPL AND GEN OR PROVIDE A |
| | DISCONNECITNG MEANS FOR FEEDERS FROM GEN |
| | ALSO. |
| | CAN NOT VEIRFY THE MEANS OF DISCONNECT |
| | FOR THE LINE SIDE POWER FROM FPL MEETING |
| | 230.70,230.76,230.79. |
| | PLEASE SEE 225.31-225.39 |
| | PLEASE SEE SPECS SUBMITTED WILL NOT BE |
| | ACCEPTABLE AS SHOWN. |
| | |
| | 3) NOTE: PLEASE INDICATE LOCATION OF ALL |
| | EQUIPMENT ON A LAYOUT FOR HOUSE. |
| | 215.. |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE ALSO INDICATE THE RATING FOR ATS. |
| | |
| | 5) NOTE: PLEASE SEE LOAD CALCULATIONS |
| | SUBMITTED SEEM TO BE MISSING MANY OTHER |
| | LOADS IN DWELLING. |
| | WASHER, LAUNDRY, DRYER, WATER HEATER, |
| | PUUMPS ETC. |
| | ANY GAS APPLIANCE SHALL BE INDICATED. |
| | PLEASE PROVIDE A COMPLETE PANEL SCHEDULE |
| | FOR INTENDED LOADS. |
| | PLEASE KNOW, IF LOADS EXCEED RATING OF |
| | GEN, LOAD SHEDDING MAY BE APPLIED, |
| | HOWEVER SHOW DETAIL. |
| | 702.5,220,220.16,220.18, ETC. |
| | 215.5 |
| | |
| | 6) NOTE: PLEASE SEE THAT THE RESPONSIBLE |
| | LICENSE CONTRACTOR SHALL PRINT NAME AND |
| | SIGN PLANS. |
| | FBC 106.2.1, 106.3.2.1 ADMIN SECT AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | 7) NOTE: PLEASE SEE THAT VALUE SHALL BE |
| | ADJUSTED TO INLCUDE ALL LABOR AND |
| | MATERIALS EVEN IF ANY EQUIPMENT ETC IS |
| | OWNER SUPPLIED. |
| | FBC 108.3 ADMINISTRATIVE SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | ** PLEASE KNOW, IF VALUE IS NOT |
| | ADJUSTED, ONE WILL BE CALCUALTE BY THIS |
| | OFFICE USING MARSHALL'S/ SWIFT GUIDE AS |
| | ADOPTED INTO THE FBC. |
| | ANY INCREASE IN VALUE SHALL BE DONE WHEN |
| | RE-SUBMITTIGN PLANS AND PERMIT |
| | APPLICATION. |
| | |
| | 8) NOTE: PLEASE BE SURE THE MANUFACTURES |
| | SPECS / CUT SHEETS SHALL INDICATE THE |
| | MIN CLEARENCES SET BY THE MANUFACTURE. |
| | 215.5 |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2006-06-08 00:00:00 | NEEDS TO UPDATE VALUE FOR TOTAL SCOPE. |
| | LOOK FOR REVIEW NOTES. FBC 108.3 |