Plan Review Notes
Plan Review Notes For Permit 06051051
Permit Number 06051051
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-13 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 225.31 DISCONNECTING MEANS.
 MEANS SHALL BE PROVIDED FOR
 DISCONNECTING ALL UNGROUNDED CONDUCTORS
 THAT SUPPLY OR PASS THROUGH THE BUILDING
 OR STRUCTURE. THIS MEANS ON THE
 BUILDING, NOT THE GENERATOR. SEE 225.36.
  
 225.32 LOCATION.
 THE DISCONNECTING MEANS SHALL BE
 INSTALLED EITHER INSIDE OR OUTSIDE OF
 THE BUILDING OR STRUCTURE SERVED OR
 WHERE THE CONDUCTORS PASS THROUGH THE
 BUILDING OR STRUCTURE. THE DISCONNECTING
 MEANS SHALL BE AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE
 OF THE CONDUCTORS. FOR THE PURPOSES OF
 THIS SECTION, THE REQUIREMENTS IN 230.6
 SHALL BE PERMITTED TO BE UTILIZED.
  
 230.72 GROUPING OF DISCONNECTS.
 (A) GENERAL. THE TWO TO SIX DISCONNECTS
 AS PERMITTED IN 230.71 SHALL BE GROUPED.
 EACH DISCONNECT SHALL BE MARKED TO
 INDICATE THE LOAD SERVED.
  
 PLEASE LOCATE ALL SERVICE EQUIPMENT ON
 THE PLAN, METER ENCLOSURE, DISCONNECTS
 AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718
  