Plan Review Notes
Plan Review Notes For Permit 06051043
Permit Number 06051043
Review Stop E
Sequence Number 5
Notes
Date Text
2007-03-10 11:27:30** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE SEE PLANS INDICATE A NEW 200AMP
 DISCONNECT INSIDE THE EXISTING 200AMP MAIN BREAKER
 PANEL? THIS IS UNCLEAR WHAT THIS IS FOR AS THE RISER
 DOES NOT INCLUDE ANY INFORMATION FOR THIS AS NEW FEED?
 PLEASE CLARIFY.
 FBC ADMIN SECTION 106.1.2
  
 2) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM. THIS WAS ON ORIGINAL PLANS
 AND NOTED ON PREVIOUS SET OF REVISIONS SUBMITTED AS IT
 WAS REMOVED.
 PLEASE SEE 250.50.
  
 3) NOTE: PLEASE SEE 210.4B AS THE DISHWASHER AND
 DISPOSAL IS REQUIRED TO BE ON A 2-POLE BREAKER WHEN
 FEEDING THE SAME DEVICE AND THE SAME YOKE.
  
 4) NOTE: PLEASE CLARIFY THE IG RECEPTACLE ON THE
 KITCHEN COUNTER SPACE?
 210.8A6
  
 5) NOTE: PLEASE SEE THE PANEL SCHEDULE FOR CIRCUITS
 SHALL BE SPECIFIC TO THE AREAS AND ROOMS THEY FEED.
 PLEASE SEE TEXT BELOW TAKEN DIRECTLY FROM THE
 COMMENTARY OF THE CODE.
 * TO REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2
  
 6) NOTE: PLEASE SEE WALL SPACE IN DINING ROOM AREA FOR
 RECEPTACLE TO BE WITHIN 6FT OF DOOR AND EACH PORTION
 THEREAFTER TO MEET 210.52.
 PLEASE SEE PLANS MENTIONS EXISTING AREA, HOWEVER PLANS
 ALSO INDICATE THE ENTIRE DWELLING BEING BROUGHT UP TO
 CODE.
  
 7) NOTE: WATER HEATER SHOWN TO HAVE A 220V RECEPTACLE
 AND IS REQUIRED TO CONTAIN DISCONNECT. 422.30, 422.31
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]