| 2007-03-10 11:27:30 | ** UNSAT 2ND REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE PLANS INDICATE A NEW 200AMP |
| | DISCONNECT INSIDE THE EXISTING 200AMP MAIN BREAKER |
| | PANEL? THIS IS UNCLEAR WHAT THIS IS FOR AS THE RISER |
| | DOES NOT INCLUDE ANY INFORMATION FOR THIS AS NEW FEED? |
| | PLEASE CLARIFY. |
| | FBC ADMIN SECTION 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM. THIS WAS ON ORIGINAL PLANS |
| | AND NOTED ON PREVIOUS SET OF REVISIONS SUBMITTED AS IT |
| | WAS REMOVED. |
| | PLEASE SEE 250.50. |
| | |
| | 3) NOTE: PLEASE SEE 210.4B AS THE DISHWASHER AND |
| | DISPOSAL IS REQUIRED TO BE ON A 2-POLE BREAKER WHEN |
| | FEEDING THE SAME DEVICE AND THE SAME YOKE. |
| | |
| | 4) NOTE: PLEASE CLARIFY THE IG RECEPTACLE ON THE |
| | KITCHEN COUNTER SPACE? |
| | 210.8A6 |
| | |
| | 5) NOTE: PLEASE SEE THE PANEL SCHEDULE FOR CIRCUITS |
| | SHALL BE SPECIFIC TO THE AREAS AND ROOMS THEY FEED. |
| | PLEASE SEE TEXT BELOW TAKEN DIRECTLY FROM THE |
| | COMMENTARY OF THE CODE. |
| | * TO REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| | SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND |
| | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| | REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE SEE WALL SPACE IN DINING ROOM AREA FOR |
| | RECEPTACLE TO BE WITHIN 6FT OF DOOR AND EACH PORTION |
| | THEREAFTER TO MEET 210.52. |
| | PLEASE SEE PLANS MENTIONS EXISTING AREA, HOWEVER PLANS |
| | ALSO INDICATE THE ENTIRE DWELLING BEING BROUGHT UP TO |
| | CODE. |
| | |
| | 7) NOTE: WATER HEATER SHOWN TO HAVE A 220V RECEPTACLE |
| | AND IS REQUIRED TO CONTAIN DISCONNECT. 422.30, 422.31 |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |