Plan Review Notes
Plan Review Notes For Permit 06051043
Permit Number 06051043
Review Stop E
Sequence Number 4
Notes
Date Text
2007-02-18 14:04:14*** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE REVISIONS TO THE DESIGNER OF
 RECORD AND HAVE PLANS RE-DRAWN WITH ALL CHANGES. PLEASE
 DO NOT SUBMIT PLANS DONE IN INK OR IN PENCIL AND HAND
 WRITTEN CHANGES.
 FBC 106.1.2, 106.3.1.
  
 2) NOTE: PLEASE SEE THE RISER NOW IS COMPLETELY REVISED
 WHICH NOW INDICATES MAIN SERVICE AS EXISTING?? PLEASE
 SEE PLANS STILL INDICATE A NEW SERVICE, NEW MAIN ETC.
 PLEASE CORRELATE AND REVISE ACCORDINGLY.
 215.5,
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE A NEW SUB PANEL IS NOW SHOWN,
 HOWEVER NOW THAT THE RISER HAS BEEN REVISED, PLEASE
 INCLUDE THE OVER CURRENT PROTECTION FROM WHAT IS NOW
 BEING SHOWN AS AN EXISTING 200AMP PANEL FOR NEW SUB
 PANEL.
 240.4, 310.16, 215.5 ETC
  
 4) NOTE: PLEASE SUBMIT A NEW PANEL SCHEDULE FOR THE NEW
 SUB PANEL WHICH IS NOW SHOWN SHOWING ALL THE OVER
 CURRENT PROTECTION DEVICES ALONG WITH THE SIZE OF THE
 BRANCH CIRCUIT CONDUCTORS FOR REVIEW.
 310.16, 240.4, 408.4 ETC.
  
 5) NOTE: PLEASE SEE THE MASTER BATH ROOM GFI WHICH IS
 BEING SHOWN ON THE ONE SIDE OF THE LAV. PLEASE SEE
 210.52D WHICH REQUIRES THE GFI WITHIN 3FT OF SINK EDGE,
 HOWEVER MAY NOT CROSS OVER SINK TO PLUG IN AN
 APPLIANCE. PLEASE ADD AN ADDITIONAL GFI OR REVISE
 LOCATION.
  
 6) NOTE: PLEASE SHOW THE GROUNDING ELECTRODE SYSTEM PER
 250.50
 (SHOWN ON ORIGINAL RISER)
  
 7) NOTE: NOTES WRITTEN ON PLANS MENTIONS A 3-WAY
 SWITCHED REQUIRED AT MASTER BEDROOM AT THE EGRESS TO
 REAR PORCH; HOWEVER THE PLANS ALREADY SHOW THIS??
 210.70
  
 8) NOTE: PLEASE SEE THAT ALL OUTSIDE RECEPTACLES ARE TO
 BE GFI/ GFI PROTECTED. 210.8A3
  
 ** PLEASE KNOW THAT DUE TO SOME INFORMATION NOT YET
 SUBMITTED FOR REVIEW THERE MAY BE COMMENTS ON THE
 FOLLOWING REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]