| Date |
Text |
| 2007-02-18 14:04:14 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE PROVIDE REVISIONS TO THE DESIGNER OF |
| | RECORD AND HAVE PLANS RE-DRAWN WITH ALL CHANGES. PLEASE |
| | DO NOT SUBMIT PLANS DONE IN INK OR IN PENCIL AND HAND |
| | WRITTEN CHANGES. |
| | FBC 106.1.2, 106.3.1. |
| | |
| | 2) NOTE: PLEASE SEE THE RISER NOW IS COMPLETELY REVISED |
| | WHICH NOW INDICATES MAIN SERVICE AS EXISTING?? PLEASE |
| | SEE PLANS STILL INDICATE A NEW SERVICE, NEW MAIN ETC. |
| | PLEASE CORRELATE AND REVISE ACCORDINGLY. |
| | 215.5, |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE A NEW SUB PANEL IS NOW SHOWN, |
| | HOWEVER NOW THAT THE RISER HAS BEEN REVISED, PLEASE |
| | INCLUDE THE OVER CURRENT PROTECTION FROM WHAT IS NOW |
| | BEING SHOWN AS AN EXISTING 200AMP PANEL FOR NEW SUB |
| | PANEL. |
| | 240.4, 310.16, 215.5 ETC |
| | |
| | 4) NOTE: PLEASE SUBMIT A NEW PANEL SCHEDULE FOR THE NEW |
| | SUB PANEL WHICH IS NOW SHOWN SHOWING ALL THE OVER |
| | CURRENT PROTECTION DEVICES ALONG WITH THE SIZE OF THE |
| | BRANCH CIRCUIT CONDUCTORS FOR REVIEW. |
| | 310.16, 240.4, 408.4 ETC. |
| | |
| | 5) NOTE: PLEASE SEE THE MASTER BATH ROOM GFI WHICH IS |
| | BEING SHOWN ON THE ONE SIDE OF THE LAV. PLEASE SEE |
| | 210.52D WHICH REQUIRES THE GFI WITHIN 3FT OF SINK EDGE, |
| | HOWEVER MAY NOT CROSS OVER SINK TO PLUG IN AN |
| | APPLIANCE. PLEASE ADD AN ADDITIONAL GFI OR REVISE |
| | LOCATION. |
| | |
| | 6) NOTE: PLEASE SHOW THE GROUNDING ELECTRODE SYSTEM PER |
| | 250.50 |
| | (SHOWN ON ORIGINAL RISER) |
| | |
| | 7) NOTE: NOTES WRITTEN ON PLANS MENTIONS A 3-WAY |
| | SWITCHED REQUIRED AT MASTER BEDROOM AT THE EGRESS TO |
| | REAR PORCH; HOWEVER THE PLANS ALREADY SHOW THIS?? |
| | 210.70 |
| | |
| | 8) NOTE: PLEASE SEE THAT ALL OUTSIDE RECEPTACLES ARE TO |
| | BE GFI/ GFI PROTECTED. 210.8A3 |
| | |
| | ** PLEASE KNOW THAT DUE TO SOME INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW THERE MAY BE COMMENTS ON THE |
| | FOLLOWING REVIEW. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |