| Plan Review Notes For Permit 06051043 |
| Permit Number |
06051043 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-09-05 00:00:00 | **** NOTES REDLINED *** | | | | | | | | | 1) NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO PANEL. | | | 250.110.25.24,250.122 | | | #6 MIN REQUIRED. | | | | | | 2) NOTE: PLEASE SEE 250.66 FOR MIN SIZE | | | FOR GROUNDING ELECTRODE CONDUCTOR. | | | PLEASE SEE #4 MIN REQUIRED. | | | | | | 3) NOTE: PLEASE SEE RISER SHOWS 1 1/2" | | | CONDUIT FROM METER TO MAIN AND MAIN TO | | | SUB PANEL. PLEASE SEE CHAPTER 9 TABLES | | | FOR MIN SIZING. PLEASE SEE A 2" CONDUIT | | | MIN IS REQUIRED. | | | | | | ** THE ABOVE WAS REDLINED, AND IF THERE | | | ARE ANY REVISIONS BEFORE ROUGH, PLEASE | | | REVISE. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 |
|