Plan Review Notes
Plan Review Notes For Permit 06051043
Permit Number 06051043
Review Stop E
Sequence Number 3
Notes
Date Text
2006-09-05 00:00:00**** NOTES REDLINED ***
  
  
 1) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110.25.24,250.122
 #6 MIN REQUIRED.
  
 2) NOTE: PLEASE SEE 250.66 FOR MIN SIZE
 FOR GROUNDING ELECTRODE CONDUCTOR.
 PLEASE SEE #4 MIN REQUIRED.
  
 3) NOTE: PLEASE SEE RISER SHOWS 1 1/2"
 CONDUIT FROM METER TO MAIN AND MAIN TO
 SUB PANEL. PLEASE SEE CHAPTER 9 TABLES
 FOR MIN SIZING. PLEASE SEE A 2" CONDUIT
 MIN IS REQUIRED.
  
 ** THE ABOVE WAS REDLINED, AND IF THERE
 ARE ANY REVISIONS BEFORE ROUGH, PLEASE
 REVISE.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717