| Date |
Text |
| 2006-08-07 00:00:00 | ******* UNSAT 2ND REVIEW ************ |
| | |
| | ** PLEASE SEE SOME COMMENTS BELOW ARE |
| | STILL IN NEED OF ADDRESSING AND PLEASE |
| | SEE NEW NOTES DUE TO CHANGES IN PLANS. |
| | NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW. NEW NOTES ADDED TO THE |
| | BOTTOM. |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE:NO, PLEASE SEE MOST AREAS HAVE |
| | BEEN DONE HOWEVER PLEASE SEE MEANS OF |
| | EGREES FROM EXISTING KITCHEN/DINING AREA |
| | THROUGH THE LIVING RM TO OUTSIDE. PLEASE |
| | SEE THIS CAN BE POSSIBLY ADDRESSED BY |
| | MEANS OF A 3-WAY SWITCH TO THE 1/2 SW |
| | RECEPT. (THIS IS ONLY ONE OPTION). |
| | PLEASE SEE FAN/LT IS STILL ONLY SHOWN AS |
| | A "J" FOR JUNCTION BOX. PLEASE KNOW, THE |
| | "J" NEEDS TO BE REMOVED AS THIS FAN AND |
| | LT WILL BE REQUIRED IF THIS METHOD IS |
| | BEING USED FOR MEANS OF EGRESS.(FAMILY |
| | RM AND REAR PORCH) |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 210.70, LS 101 7.8, |
| | MANY LOCATIONS ON PLANS INDICATE A |
| | J-BOX, YET ALSO MENTIONS AFAN AND LT? |
| | PLEASE SEE IF A FAN LT IS NOTED, THEN |
| | THESE SHOULD BE SHOWN. |
| | **SEPARATE** |
| | ** THIS IS ONLY A NOTICED AS PLANS ONLY |
| | INDICATE ONE SWITCH FOR BOTH. THIS IS |
| | OK, HOWEVER ONLY NOTED. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: NO/OK, PLEASE SEE ONLY ONE |
| | STILL MISSING. THIS COULD HAVE BEEN |
| | REDLINED, HOWEVER PLANS ARE COMING BACK |
| | FOR OTHER COMMENTS PLEASE ADRESS AT THIS |
| | TIME. (BEDRM #2) |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MANY RECEPTS MISSING |
| | PER 210.52 |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: OK, HOWEVER PLEASE SEE NEW |
| | COMMENTS DUE TO THE RISER BEING REVISED |
| | FROM THE PREVIOUS SET OF PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 250.6 AND 250.24B |
| | FOR EQUIPMENT GROUNDING CONDUCTOR SHALL |
| | NOT BE INSTALLED BEFORE THE FIRST MEANS |
| | OF DISCONNECT FOR OBJECTIONAL CURRENTS. |
| | |
| | 8) NOTE: NO, PLEASE SEE PLANS NOW ONLY |
| | SHOW AFCI PROTECTION FOR RECEPTS. PLEASE |
| | KNOW, AFCI (ARC FAULT ) PROTECTION IS |
| | REQUIRED FOR ALL "OUTLETS"IN BEDRMS. |
| | THIS INCLUDES THE ENTIRE BRANCH |
| | CIRCUITS. PLEASE SEE THIS INLCUDES SD'S, |
| | LTS, FANS ETC. PLEASE KNOW THE |
| | REQUIREMENT FOR ONLY RECEPTS WENT OUT |
| | WITH THE 1999 NEC. |
| | PLEASE LIST ON PANEL SCHEDULE AS |
| | PREVIOUSLY REQUESTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING LISTED ARC |
| | FAULT CIRCUITS ON PANEL SCHEDULE. |
| | 210.12B |
| | |
| | 9) NOTE: NO, PLEASE SEE THIS WAS |
| | ADDRESSED AND ADDED AIC RATING TO MCB |
| | PANEL IN GARAGE, HOWEVER PLEASE SEE |
| | RISER NOW SHOWS A NEW MAIN DISCONNECT |
| | WHICH DOES NOT INDICATE RATINGS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING AIC RATING |
| | FOR NEW MAINS/PANEL. |
| | 110.9,90.8 |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: NO? PLEASE SEE NO COMMENTS |
| | WERE MADE IF THIS IS FED UNDERGROUND AND |
| | NOW RISER HAS BEEN REVISED TO SHOW WHAT |
| | APPEARS TO BE A DISCONNECT ON THE LINE |
| | SIDE OF THE MCB [ANEL. PLEASE SEE NO |
| | INFORMATION WAS SUBMITTED FOR THIS NEW |
| | MAIN DISCONNECT AND PLEASE SEE PLANS DO |
| | NOT REFLECT A MAIN DISCONNECT NEXT TO |
| | METER CAN. SEE NEW COMMENTS ALSO AS THIS |
| | MAIN BEING ADDED CHANGES THE GROUNDING. |
| | |
| | ** PREVIUOUS REVIEW NOTE ** |
| | PLEASE SPECIFY OF NEW FEED |
| | FROM METER TO MAIN IS UNDERGROUND? |
| | PLEASE SEE 230.70, NO MORE THAN 8' OF |
| | UNPROTECTED CONDUCTORS ARE PERMITTED |
| | INSIDE THE BUILDING WITH HAVING A |
| | DISCONNECT AND OCP ON THE OUTSIDE OF THE |
| | DWELLING. |
| | 240.6 |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: NO, PLEASE SEE NEC 220 FOR TWO |
| | POSSIBLE METHODS FOR CALCULATING LOADS |
| | FOR A SINGLE FAMILY DWELLING. PLEASE SEE |
| | CALCS AS SHOWN DO NOT MEET EITHER ONE. |
| | PLEASE SEE CODE DOES NOT PERMIT DERATING |
| | OF THE A/C/HEAT LOADS WITH THE GEN LTS |
| | NAD RECEPTS LOADS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE CALCULATIONS NEED |
| | TO MEET CODE.220,,215.5 |
| | |
| | 13) NOTE: OK, PLEASE BE SURE TO DO THIS |
| | ON REVISED PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE PRINTED NAME |
| | AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR PLANS AND DESIGN IS MISSING. |
| | FBC 106.2.1 ADMIN SECT AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 14) NOTE: NO/OK, PLEASE SEE TWO WERE |
| | ADDED ONE FOR MASTER AND ONE FOR NEW |
| | CABANNA BATH. PLEASE SEE OTHER BATH(S). |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH(S) CIRCUITS PER |
| | 210.52D,210.11C3 |
| | MUST BE 20A AND #12. |
| | PLEASE SEE ONE BATH INDICATES THIS. |
| | |
| | 15) NOTE: OK. |
| | |
| | ** NEW NOTES** |
| | |
| | 16) NOTE: PLEASE SEE RISER DIAGRAM, IF A |
| | MAIN IS NOW ADDED TO THE LINE SIDE OF |
| | THE MCB PANEL, PLEASE SEE MISSING |
| | EQUIPMENT GROUNDING CONDUCTOR FROM MAIN |
| | TO THE PANEL. |
| | 250.24B, 250.110,250.122 |
| | |
| | 17) NOTE: PLEASE SEE MISSING AHU #2 OR |
| | #1? PLEASE SEE PLANS ONLY SHOW ONE AHU?? |
| | PLEASE CLARIFY AND SHOW LOCATION OF THIS |
| | AHU. PLEASE BE SURE TO INDICATE |
| | LT/RECEPTS. 210.70, 210.63 |
| | DISCONNECT PER440.11 |
| | PLEASE SEE MIN CLEARENCE FOR UC. 110.26 |
| | |
| | 18) NOTE: PLEASE SEE KITCHEN COUNTER |
| | SPACE AS THE GFI REQUIRED ALONG KITCHEN |
| | COUNTER IS BEING NOTED AS "UC". (UNDER |
| | CABINET). |
| | PLEASE ALSO SEE DISPOSAL IS BEING SHOWN |
| | AS A GFI RECEPT. |
| | 210.52C1-5. (C-3) C-5) |
| | |
| | 19) NOTE: PLEASE SEE SD NOW SHOWN |
| | OUTSIDEMASTER BEDRM IS REQUIRED TO BE |
| | WITH THE 12" OF THE HIGHEST POINT ON ANY |
| | FLAT OR TRAY CEILING. PLEASE SEE NFPA-72 |
| | 11.8.3 |
| | PLEASE KNOW, IF TRAY IS LESS THAN 12" |
| | THEN IT IS OK WHERE IT IS. THIS ONE |
| | COMMENT WAS MISSED ON PREVIOUS REVIEW. |
| | THIS COULD HAVE BEEN REDLINED, HOWEVER |
| | PLANS ARE COMING BACK FOR OTHER |
| | COMMENTS. |
| | |
| | 20) NOTE: PLEASE SEE FS 553.80(2)(B) |
| | WITH RESOECT TO REPEAT COMMENTS. |
| | |
| | ** IMPORTANT** |
| | WHEN RESUBMITTING PLANS , PLEASE |
| | COMPLETELY REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW. |
| | PLEASE ONLY SUBMIT ONE COPY OF THE |
| | OLD/VOIDED REMOVED SHEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |