Plan Review Notes
Plan Review Notes For Permit 06051043
Permit Number 06051043
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-07 00:00:00******* UNSAT 2ND REVIEW ************
  
 ** PLEASE SEE SOME COMMENTS BELOW ARE
 STILL IN NEED OF ADDRESSING AND PLEASE
 SEE NEW NOTES DUE TO CHANGES IN PLANS.
 NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW. NEW NOTES ADDED TO THE
 BOTTOM.
  
 1) NOTE: OK.
  
 2) NOTE:NO, PLEASE SEE MOST AREAS HAVE
 BEEN DONE HOWEVER PLEASE SEE MEANS OF
 EGREES FROM EXISTING KITCHEN/DINING AREA
 THROUGH THE LIVING RM TO OUTSIDE. PLEASE
 SEE THIS CAN BE POSSIBLY ADDRESSED BY
 MEANS OF A 3-WAY SWITCH TO THE 1/2 SW
 RECEPT. (THIS IS ONLY ONE OPTION).
 PLEASE SEE FAN/LT IS STILL ONLY SHOWN AS
 A "J" FOR JUNCTION BOX. PLEASE KNOW, THE
 "J" NEEDS TO BE REMOVED AS THIS FAN AND
 LT WILL BE REQUIRED IF THIS METHOD IS
 BEING USED FOR MEANS OF EGRESS.(FAMILY
 RM AND REAR PORCH)
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.70, LS 101 7.8,
 MANY LOCATIONS ON PLANS INDICATE A
 J-BOX, YET ALSO MENTIONS AFAN AND LT?
 PLEASE SEE IF A FAN LT IS NOTED, THEN
 THESE SHOULD BE SHOWN.
 **SEPARATE**
 ** THIS IS ONLY A NOTICED AS PLANS ONLY
 INDICATE ONE SWITCH FOR BOTH. THIS IS
 OK, HOWEVER ONLY NOTED.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: NO/OK, PLEASE SEE ONLY ONE
 STILL MISSING. THIS COULD HAVE BEEN
 REDLINED, HOWEVER PLANS ARE COMING BACK
 FOR OTHER COMMENTS PLEASE ADRESS AT THIS
 TIME. (BEDRM #2)
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MANY RECEPTS MISSING
 PER 210.52
  
 6) NOTE: OK.
  
 7) NOTE: OK, HOWEVER PLEASE SEE NEW
 COMMENTS DUE TO THE RISER BEING REVISED
 FROM THE PREVIOUS SET OF PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.6 AND 250.24B
 FOR EQUIPMENT GROUNDING CONDUCTOR SHALL
 NOT BE INSTALLED BEFORE THE FIRST MEANS
 OF DISCONNECT FOR OBJECTIONAL CURRENTS.
  
 8) NOTE: NO, PLEASE SEE PLANS NOW ONLY
 SHOW AFCI PROTECTION FOR RECEPTS. PLEASE
 KNOW, AFCI (ARC FAULT ) PROTECTION IS
 REQUIRED FOR ALL "OUTLETS"IN BEDRMS.
 THIS INCLUDES THE ENTIRE BRANCH
 CIRCUITS. PLEASE SEE THIS INLCUDES SD'S,
 LTS, FANS ETC. PLEASE KNOW THE
 REQUIREMENT FOR ONLY RECEPTS WENT OUT
 WITH THE 1999 NEC.
 PLEASE LIST ON PANEL SCHEDULE AS
 PREVIOUSLY REQUESTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING LISTED ARC
 FAULT CIRCUITS ON PANEL SCHEDULE.
 210.12B
  
 9) NOTE: NO, PLEASE SEE THIS WAS
 ADDRESSED AND ADDED AIC RATING TO MCB
 PANEL IN GARAGE, HOWEVER PLEASE SEE
 RISER NOW SHOWS A NEW MAIN DISCONNECT
 WHICH DOES NOT INDICATE RATINGS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING AIC RATING
 FOR NEW MAINS/PANEL.
 110.9,90.8
 FBC 106.1.2
  
 10) NOTE: NO? PLEASE SEE NO COMMENTS
 WERE MADE IF THIS IS FED UNDERGROUND AND
 NOW RISER HAS BEEN REVISED TO SHOW WHAT
 APPEARS TO BE A DISCONNECT ON THE LINE
 SIDE OF THE MCB [ANEL. PLEASE SEE NO
 INFORMATION WAS SUBMITTED FOR THIS NEW
 MAIN DISCONNECT AND PLEASE SEE PLANS DO
 NOT REFLECT A MAIN DISCONNECT NEXT TO
 METER CAN. SEE NEW COMMENTS ALSO AS THIS
 MAIN BEING ADDED CHANGES THE GROUNDING.
  
 ** PREVIUOUS REVIEW NOTE **
 PLEASE SPECIFY OF NEW FEED
 FROM METER TO MAIN IS UNDERGROUND?
 PLEASE SEE 230.70, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS ARE PERMITTED
 INSIDE THE BUILDING WITH HAVING A
 DISCONNECT AND OCP ON THE OUTSIDE OF THE
 DWELLING.
 240.6
  
 11) NOTE: OK.
  
 12) NOTE: NO, PLEASE SEE NEC 220 FOR TWO
 POSSIBLE METHODS FOR CALCULATING LOADS
 FOR A SINGLE FAMILY DWELLING. PLEASE SEE
 CALCS AS SHOWN DO NOT MEET EITHER ONE.
 PLEASE SEE CODE DOES NOT PERMIT DERATING
 OF THE A/C/HEAT LOADS WITH THE GEN LTS
 NAD RECEPTS LOADS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE CALCULATIONS NEED
 TO MEET CODE.220,,215.5
  
 13) NOTE: OK, PLEASE BE SURE TO DO THIS
 ON REVISED PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR PLANS AND DESIGN IS MISSING.
 FBC 106.2.1 ADMIN SECT AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 14) NOTE: NO/OK, PLEASE SEE TWO WERE
 ADDED ONE FOR MASTER AND ONE FOR NEW
 CABANNA BATH. PLEASE SEE OTHER BATH(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) CIRCUITS PER
 210.52D,210.11C3
 MUST BE 20A AND #12.
 PLEASE SEE ONE BATH INDICATES THIS.
  
 15) NOTE: OK.
  
 ** NEW NOTES**
  
 16) NOTE: PLEASE SEE RISER DIAGRAM, IF A
 MAIN IS NOW ADDED TO THE LINE SIDE OF
 THE MCB PANEL, PLEASE SEE MISSING
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO THE PANEL.
 250.24B, 250.110,250.122
  
 17) NOTE: PLEASE SEE MISSING AHU #2 OR
 #1? PLEASE SEE PLANS ONLY SHOW ONE AHU??
 PLEASE CLARIFY AND SHOW LOCATION OF THIS
 AHU. PLEASE BE SURE TO INDICATE
 LT/RECEPTS. 210.70, 210.63
 DISCONNECT PER440.11
 PLEASE SEE MIN CLEARENCE FOR UC. 110.26
  
 18) NOTE: PLEASE SEE KITCHEN COUNTER
 SPACE AS THE GFI REQUIRED ALONG KITCHEN
 COUNTER IS BEING NOTED AS "UC". (UNDER
 CABINET).
 PLEASE ALSO SEE DISPOSAL IS BEING SHOWN
 AS A GFI RECEPT.
 210.52C1-5. (C-3) C-5)
  
 19) NOTE: PLEASE SEE SD NOW SHOWN
 OUTSIDEMASTER BEDRM IS REQUIRED TO BE
 WITH THE 12" OF THE HIGHEST POINT ON ANY
 FLAT OR TRAY CEILING. PLEASE SEE NFPA-72
 11.8.3
 PLEASE KNOW, IF TRAY IS LESS THAN 12"
 THEN IT IS OK WHERE IT IS. THIS ONE
 COMMENT WAS MISSED ON PREVIOUS REVIEW.
 THIS COULD HAVE BEEN REDLINED, HOWEVER
 PLANS ARE COMING BACK FOR OTHER
 COMMENTS.
  
 20) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESOECT TO REPEAT COMMENTS.
  
 ** IMPORTANT**
 WHEN RESUBMITTING PLANS , PLEASE
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW.
 PLEASE ONLY SUBMIT ONE COPY OF THE
 OLD/VOIDED REMOVED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  