2006-06-16 00:00:00DENIED;
 1.RISER DIAGRAM NOT TO CODE, NOT
 PROPERLY VENTED.
 2.DELETE NOTE 15, AN ENGINEERED WATER
 HAMMER ARRESTOR IS REQUIRED WHERE QUICK
 CLOSING VALVES EXIST. SEE SEC.604.9.
 3.WASHING MACHINE DETAIL; DISCHARGE PIPE
 TO BE 3" SEC. 406.3, A CLEANOUT IS
 REQUIRED AT 48" AFF.,AND WATER HAMMER
 ARRESTORS ARE REQUIRED.
 ONE SET OF PLANS MARKED IN RED.