| 2006-06-16 00:00:00 | *** DENIED *** |
| | 1) ENERGY CAL'S. AER CALLING FOR A 4 TON |
| | A/C SYSTEM, MANUAL J CAL'S. ARE CALLING |
| | FOR A 2.6 TON A/C SYSTEM, AND THE |
| | MECHANICAL PLANS ARE CALLING FOR A 4 TON |
| | A/C SYSTEM BUT THE MODEL NUMBERS AND |
| | BTU'S ARE FOR A 3 TON SYSTEM, PLEASE |
| | CORRECT. |
| | |
| | 2) ENERGY CAL'S. ARE CALLING FOR A 12 |
| | SEER A/C SYSTEM, AND THE MECHANICAL |
| | PLANS ARE CALLING FOR A 10.3 SEER A/C |
| | SYSTEM, THE PLANS CAN NOT CALL FOR LESS |
| | THAN THE ENERGY CAL'S. PLEASE CORRECT. |
| | |
| | 3) ENERGY CAL'S. AER SHOWING NO HEAT, |
| | THE A/C PLANS AER SHOWING 10 KW HEATER |
| | PLEASE CORRECT, PLEASE NOTE 10 KW DOES |
| | NOT = 28,000 BTU'S PLEASE CORRECT ON |
| | PLANS. |
| | |
| | 4) CORRECTED ENERGY CAL'S. NEED TO BE |
| | SIGNED IN TWO PLACES AT THE BOTTOM. |
| | |
| | 5) MECHANICAL PLANS ARE NOT SHOWING THE |
| | SIZE OF THE SUPPLY AIR DUCT LEAVING THE |
| | AIR HANDLER. |
| | |
| | 6) RETURN AIR DUCT LEAVING THE AIR |
| | HANDLER IS NOT SIZED. |
| | |
| | 7) SHOW THE CFM'S AT EACH SUPPLY AIR |
| | GRILL. |
| | |
| | 8) SHOW THE SIZE OF EACH RETURN AIR |
| | GRILL. |
| | |
| | 9) SHOW THE CLOTHES DRYER VENT AND |
| | TERMINATION ON MECHANICAL PLANS, PLEASE |
| | NOTE: CLOTHES DRYER VENT TERMINATION |
| | MUST BE A MIN. OF 4 FT. FROM A/C |
| | CONDENSER UNIT, PER 2004 FBC/M 501.2 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |