Plan Review Notes
Plan Review Notes For Permit 06051043
Permit Number 06051043
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-14 00:00:00*********** UNSAT ************
  
 1) NOTE: PLEASE SEE PLANS NEED TO
 REFLECT AND MEET 2002 NEC.PLEASE SEE
 PLANS REFERENCE BOTH 2002 AND 2005
  
 2) NOTE: PLEASE SEE 210.70, LS 101 7.8,
 MANY LOCATIONS ON PLANS INDICATE A
 J-BOX, YET ALSO MENTIONS AFAN AND LT?
 PLEASE SEE IF A FAN LT IS NOTED, THEN
 THESE SHOULD BE SHOWN.
 **SEPARATE**
 ** THIS IS ONLY A NOTICED AS PLANS ONLY
 INDICATE ONE SWITCH FOR BOTH. THIS IS
 OK, HOWEVER ONLY NOTED.
  
 3) NOTE: PLEASE SEE MISSING FOOTER STEEL
 PER 250.50.
  
 4) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52D, 210.11C3, 210.8A
  
 5) NOTE: PLEASE SEE MANY RECEPTS MISSING
 PER 210.52
  
 6) NOTE: PLEASE SEE SEC'S ARE TOO
 SMALL, 310.16,310.15B6,240.4,240.6 ETC
  
 7) NOTE: PLEASE SEE 250.6 AND 250.24B
 FOR EQUIPMENT GROUNDING CONDUCTOR SHALL
 NOT BE INSTALLED BEFORE THE FIRST MEANS
 OF DISCONNECT FOR OBJECTIONAL CURRENTS.
  
 8) NOTE: PLEASE SEE MISSING LISTED ARC
 FAULT CIRCUITS ON PANEL SCHEDULE.
 210.12B
  
 9) NOTE: PLEASE SEE MISSING AIC RATING
 FOR NEW MAINS/PANEL.
 215.5,110.9
  
 10) NOTE: PLEASE SPECIFY OF NEW FEED
 FROM METER TO MAIN IS UNDERGROUND?
 PLEASE SEE 230.70, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS ARE PERMITTED
 INSIDE THE BUILDING WITH HAVING A
 DISCONNECT AND OCP ON THE OUTSIDE OF THE
 DWELLING.
 240.6
  
 11) NOTE: PLEASE SEE MIN AND MAX OCP FOR
 BOTH AHU'S NEEDS TO BE ADJUSTED.
 MIN 125%, MAX 150%.
 PLEASE SEE SIZE ON ONE IS TOO HIGH AND
 THE OTHER IS TOO LOW.
 PLEASE ALSO SEE CONDUCTORS FOR AHU#2
 NEED TO MEET 310.16, 240.4
  
 12) NOTE: PLEASE SEE CALCULATIONS NEED
 TO MEET CODE.220,,215.5
  
 13) NOTE: PLEASE SEE THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR PLANS AND DESIGN IS MISSING.
 FBC 106.2.1 ADMIN SECT AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 14) NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) CIRCUITS PER
 210.52D,210.11C3
 MUST BE 20A AND #12.
 PLEASE SEE ONE BATH INDICATES THIS.
  
 15) NOTE: PLEASE SEE MISSING ELECTRICAL
 RECEPTS FOR RANGE/STOVE.
 215.5
  
 ** IMPORTANT**
 WHEN RESUBMITTING PLANS , PLEASE
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW.
 PLEASE ONLY SUBMIT ONE COPY OF THE
 OLD/VOIDED REMOVED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW