| Date |
Text |
| 2006-06-14 00:00:00 | *********** UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE PLANS NEED TO |
| | REFLECT AND MEET 2002 NEC.PLEASE SEE |
| | PLANS REFERENCE BOTH 2002 AND 2005 |
| | |
| | 2) NOTE: PLEASE SEE 210.70, LS 101 7.8, |
| | MANY LOCATIONS ON PLANS INDICATE A |
| | J-BOX, YET ALSO MENTIONS AFAN AND LT? |
| | PLEASE SEE IF A FAN LT IS NOTED, THEN |
| | THESE SHOULD BE SHOWN. |
| | **SEPARATE** |
| | ** THIS IS ONLY A NOTICED AS PLANS ONLY |
| | INDICATE ONE SWITCH FOR BOTH. THIS IS |
| | OK, HOWEVER ONLY NOTED. |
| | |
| | 3) NOTE: PLEASE SEE MISSING FOOTER STEEL |
| | PER 250.50. |
| | |
| | 4) NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52D, 210.11C3, 210.8A |
| | |
| | 5) NOTE: PLEASE SEE MANY RECEPTS MISSING |
| | PER 210.52 |
| | |
| | 6) NOTE: PLEASE SEE SEC'S ARE TOO |
| | SMALL, 310.16,310.15B6,240.4,240.6 ETC |
| | |
| | 7) NOTE: PLEASE SEE 250.6 AND 250.24B |
| | FOR EQUIPMENT GROUNDING CONDUCTOR SHALL |
| | NOT BE INSTALLED BEFORE THE FIRST MEANS |
| | OF DISCONNECT FOR OBJECTIONAL CURRENTS. |
| | |
| | 8) NOTE: PLEASE SEE MISSING LISTED ARC |
| | FAULT CIRCUITS ON PANEL SCHEDULE. |
| | 210.12B |
| | |
| | 9) NOTE: PLEASE SEE MISSING AIC RATING |
| | FOR NEW MAINS/PANEL. |
| | 215.5,110.9 |
| | |
| | 10) NOTE: PLEASE SPECIFY OF NEW FEED |
| | FROM METER TO MAIN IS UNDERGROUND? |
| | PLEASE SEE 230.70, NO MORE THAN 8' OF |
| | UNPROTECTED CONDUCTORS ARE PERMITTED |
| | INSIDE THE BUILDING WITH HAVING A |
| | DISCONNECT AND OCP ON THE OUTSIDE OF THE |
| | DWELLING. |
| | 240.6 |
| | |
| | 11) NOTE: PLEASE SEE MIN AND MAX OCP FOR |
| | BOTH AHU'S NEEDS TO BE ADJUSTED. |
| | MIN 125%, MAX 150%. |
| | PLEASE SEE SIZE ON ONE IS TOO HIGH AND |
| | THE OTHER IS TOO LOW. |
| | PLEASE ALSO SEE CONDUCTORS FOR AHU#2 |
| | NEED TO MEET 310.16, 240.4 |
| | |
| | 12) NOTE: PLEASE SEE CALCULATIONS NEED |
| | TO MEET CODE.220,,215.5 |
| | |
| | 13) NOTE: PLEASE SEE THE PRINTED NAME |
| | AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR PLANS AND DESIGN IS MISSING. |
| | FBC 106.2.1 ADMIN SECT AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 14) NOTE: PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH(S) CIRCUITS PER |
| | 210.52D,210.11C3 |
| | MUST BE 20A AND #12. |
| | PLEASE SEE ONE BATH INDICATES THIS. |
| | |
| | 15) NOTE: PLEASE SEE MISSING ELECTRICAL |
| | RECEPTS FOR RANGE/STOVE. |
| | 215.5 |
| | |
| | ** IMPORTANT** |
| | WHEN RESUBMITTING PLANS , PLEASE |
| | COMPLETELY REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW. |
| | PLEASE ONLY SUBMIT ONE COPY OF THE |
| | OLD/VOIDED REMOVED SHEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |