Plan Review Notes
Plan Review Notes For Permit 06051022
Permit Number 06051022
Review Stop M
Sequence Number 2
Notes
Date Text
2006-07-12 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 5-31-06
 NOTE #1, PLEASE SHOW DETAILED
 INFORMATION ON, ANCHORING A/C CONDENSER
 UNIT "STAND" TO THE ROOF, AND STATE THAT
 IT WILL WITHSTAND 140 MPH WINDS, PER
 2004 FBC 1609. (SEE MECHANICAL PLAN PAGE
 M3.0).
  
 2) SEE MECHANICAL PLAN PAGE M3.0 .
 CABLES ARE NOT PERMITED TO OVERLAP
 CONDENSER UNITS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  