| Plan Review Notes For Permit 06051022 |
| Permit Number |
06051022 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-01 00:00:00 | DENIED; | | | 1.SANITARY RISER DIAGRAM; MOP SINK TO GO | | | TO GREASY WASTE NOT SANITARY. | | | 2.WATER RISER DIAGRAM; WATER HAMMER | | | ARRESTORS TO BE INSTALLED PER. FBC-2004 | | | PLUMBING SEC. 604.9 AND MANUFATURE"S | | | INSTALLATION INSRUCTIONS, AS CLOSE TO | | | THE SOURCE OF HAMMER AS POSSIBLE. | | | 3.PAGE A0.0 AND P3.0, ADD TO NOTES "NO | | | DEAD ENDS ARE PROHIBITED PER SEC. 704.5 | | | DEMO PLUMBING INSPECTION REQUIRED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|