Plan Review Notes
Plan Review Notes For Permit 06051022
Permit Number 06051022
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-01 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM; MOP SINK TO GO
 TO GREASY WASTE NOT SANITARY.
 2.WATER RISER DIAGRAM; WATER HAMMER
 ARRESTORS TO BE INSTALLED PER. FBC-2004
 PLUMBING SEC. 604.9 AND MANUFATURE"S
 INSTALLATION INSRUCTIONS, AS CLOSE TO
 THE SOURCE OF HAMMER AS POSSIBLE.
 3.PAGE A0.0 AND P3.0, ADD TO NOTES "NO
 DEAD ENDS ARE PROHIBITED PER SEC. 704.5
 DEMO PLUMBING INSPECTION REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695