| Plan Review Notes For Permit 06051022 |
| Permit Number |
06051022 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-09 00:00:00 | | | | NONCOMPLIANT | | | | | | 1} SHOW THE SERVICE MAIN DISCONNECT | | | LOCATION ON A SITE PLAN. | | | | | | 2} PROVIDE A LOAD CALCULATION FOR THE | | | SERVICE SUPPLYING THESE SUB-PANELS. | | | | | | 3} PLEASE PROVIDE CONDUCTOR SIZES ON THE | | | PANEL SCHEDULE SO THAT BRANCH/FEEDER | | | CIRCUIT CONDUCTOR AND OVER CURRENT | | | PROTECTION COMPLIANCE MAY BE REVIEWED | | | PER 106.3.5.4 FBC AS AMENDED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | |
|