Plan Review Notes
Plan Review Notes For Permit 06051022
Permit Number 06051022
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-09 00:00:00 
 NONCOMPLIANT
  
 1} SHOW THE SERVICE MAIN DISCONNECT
 LOCATION ON A SITE PLAN.
  
 2} PROVIDE A LOAD CALCULATION FOR THE
 SERVICE SUPPLYING THESE SUB-PANELS.
  
 3} PLEASE PROVIDE CONDUCTOR SIZES ON THE
 PANEL SCHEDULE SO THAT BRANCH/FEEDER
 CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED
 PER 106.3.5.4 FBC AS AMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW