Plan Review Notes
Plan Review Notes For Permit 06051007
Permit Number 06051007
Review Stop B
Sequence Number 2
Notes
Date Text
2006-08-04 00:00:00PERMIT: 06051007
 ADD: 2001 PALM BCH LAKES BLVD.
 CONT: RIZNICK CONSTRUCTION
 TEL: ( )584-0363
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)COMPLIED.
  
 2) 2ND REQUEST: MISSING SOILS REPORT,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE
 SOIL IS IN DOUBT, OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH
 1802.6 .
  
 3) COMPLIED.
  
 3B) COMPLIED.
  
 3C)MISSING MINIMUM DESIGN CRITERIA:
 3C)(B) PROPOSED USE: SHEET A-1
 PROJECT DATA SUMMARY, THE DESIGNER IS
 NOT DISTINGIUSHING BETWEEN THE ZONING
 AND BUILDING TERMINOLOGY. ONCE THE
 DESIGNER STARTS TO LIST BUILDING CODE
 EDITION, THE TERMINOLOGY WILL BE AS WHAT
 IS REQUIRED IN SECTION 110.1.2*PROPOSED
 USE BUSINESS "GROUP B" SEE 304.1.
  
 3D) OCCUPANT LOAD: SEE TABLE 1004.1.4
 BUISINESS AREAS/ 100 GROSS
  
 3B)(E-I) COMPLIED.
  
 3D) 2ND REQUEST:
 3D) MISSING THE WIND DESIGN INTERNAL
 PRESSURE COEFFICIENT WHEN DESIGNED TO
 ASCE 7-02. 1603.1.4(4) THE APPLICABLE
 ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE
 COEFFICIENT.
 THE STATEMENT ABOVE MAY BE ABIT
 MISLEADING. THE FIRST REVIEW THE PLANS
 CAME INDICATING THEY ERE DESIGNED TO
 ASCE 7-98. THE STATEMENT THAT I WAS
 TRYINF TO MAKE IS (2) FOLD.
 (I) THE DESIGNER HAS THE OPTION TO
 DESIGN TO EITHER ASCE 7-02 OR TSKE THE
 EXCEPTION (1) AND DESIGN TO 1609.6.
 (II) IF THE DESIGNER DOES DESIGN TO
 ASCE 7-02 THE TERM THAT SHOULD OF BEEN
 USED IS "ENCLOSURE CLASSIFICATION"NOT
 INTERNAL PRESSURE COEFFICIENT.
 THIS BUILDING WHEN DESIGNED TO ASCE
 7-02 SHALL BE CLASSIFIED AS EITHER
 PARTIALLY OPEN OR OPEN.
 SEE SECTION 6.5.12 FOR PARTIALLY OPEN
 AND THE COEFFICIENT, IF THE OPEN
 CLASSIFICATION (SEE 6.5.13) IS
 APPLICABLE USE THE CORRECT COEFFICIENT.
  
 4) 2ND REQUEST, 4) PROVIDE ADDITIONAL
 INFORMATION, PERMIT APPLICATION PROJECT
 DESCRIPTION, IS ONLY FOR DRIVE THROUGH
 AND NOT LANDSCAPING, REPAVING OR CURBING
 OR STRIPING OF THE CURRENT SITE? IF SO
 INCLUDE UNDER PERMIT DESCPTION.
  
 5) COMPLIED.
  
 6) 2ND REQUEST,A-2/ A-3 BOTH INDICATE
 THE USE OF (2), NOW(4) SCUPPERS ON THE
 EAST AND WEST ELEVATIONS, PLANS DO NOT
 INDICATE OVERFLOW SCUPPERS. 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW
 WATER IS NOT PROVIDED, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS OR PARAPETS NOT
 LESS THAN 2 INCHES (51 MM) NOR MORE THAN
 4 INCHES (102 MM) ABOVE THE FINISHED
 ROOF COVERING AND SHALL BE LOCATED AS
 CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS. AN OVERFLOW SCUPPER
 SHALL BE SIZED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, PLUMBING.
 A-4 NOW INDICATES THERE ARE (4)
 THROUGH THE WALL SCUPPERS SHOWN ON A-4.
 I BELIEVE THERE IS A DIFFERENCE IN
 UNDERSTANDING OF TERMINOLGY IN THIS CODE
 SECTION.
 SEE 1503.4.2 SCUPPERS: WHERE REQUIRED
 FOR ROOF DRAINAGE, A SCUPPER SHALL BE
 PLACED "LEVEL" WITH THE ROOF SURFACE IN
 A WALL OR PARAPET. THE SCUPPER SHALL BE
 LOCATED AS DETERMINED BY THE SLOPE AND
 THE CONTRIBUTING AREA OF THE ROOF. THE
 EXTERIOR FACING OR LINING OF A SCUPPER,
 IF METAL, SHALL BE THE SAME AS FLASHING
 MATERIAL REQUIRED BY SECTIONS 1503
 THROUGH 1510 FOR THE PARTICULAR TYPE OF
 COVERING SPECIFIED FOR THE BUILDING. FOR
 OTHER TYPE MATERIALS, FOLLOW
 MANUFACTURER?S SPECIFICATIONS.
 THE CODE SECTION STATED IN 1503.4.3
 IS THE REQUIREMENT FOR ADDITIONAL
 OVERFLOW SCUPPERS IN CASE THE SCUPPERS
 LOCATED AT THE ROOF LEVEL ARE BLOCKED.
 FOR EACH SCUPPER AN ADDITIONAL OVERFLOW
 SCUPPER WILL BE REQUIRED, LOCATED WITH
 THE BOTTOM OF THE SCUPPER LOCATED
 BETWEEN 2"-4" ABOVE THE FINISHED ROOF.
  
 7) COMPLIED.
  
 8) 2ND REQUEST, SHEET A-3 NOTE FOR USE
 OF ALTERNATE MATERIALS FOR CEILING
 APPLICATION.
 PROVIDE ADDTIONAL INFORMATION ON THE
 TYPE OF WIRE LATH TO BE USED?
 2510.3INSTALLATION OF THESE MATERIALS
 SHALL BE IN COMPLIANCE WITH ASTM C 926
 AND ASTM C 1063.
 RULE 9B-72 PRODUCT APPROVAL FOR "PROROC
 EXTERIOR SOFFIT BOARD W/ FLORIDA STATE
 APPROVAL.
 104.1.1* ALTERNATE MATERIALS, DESIGN
 & METHODS OF CONSTRUCTION & EQUIPMENT.
 THE PROVISIONS OF THIS CODE ARE NOT
 INTENDED TO PREVENT THE INSTALLATION OF
 ANY MATERIAL OR TO PROHIBIT ANY DESIGN
 OR METHOD OF CONSTRUCTION NOT
 SPECIFICALLY PRESCRIBED BY THIS CODE,
 PROVIDED THAT ANY SUCH ALTERNATIVE HAS
 BEEN APPROVED. AN ALTERNATE MATERIAL,
 DESIGN OR METHOD OF CONSTRUCTION SHALL
 BE APPROVED WHERE THE BUILDING OFFICIAL
 FINDS THAT THE PROPOSED DESIGN IS
 SATISFACTORY AND COMPLIES WITH THE
 INTENT OF THE PROVISIONS OF THIS CODE,
 AND THAT THE MATERIAL, METHOD OR WORK
 OFFERED IS, FOR THE PURPOSE INTENDED, AT
 LEAST THE EQUIVALENT OF THAT PRESCRIBED
 IN THIS CODE IN QUANITY, STRENGTH,
 EFFECTIVENESS FIRE RESISTANCE,
 DURABILITY AND SAFETY. WHEN ALTERNATE
 LIFE SAFETY SYSTEMS ARE DESIGNED, THE
 SFPE ENGINEERING GUIDE TO
 PERFORMANCE-BASED FIRE PROTECTION
 ANALYSIS AND DESIGN OF BUILDINGS , OR
 OTHER METHODS APPROVED BY THE BUILDING
 OFFICIAL MAY BE USED. THE BUILDING
 OFFICIAL SHALL REQUIRE THAT SUFFICIENT
 EVIDENCE OR PROOF BE SUBMITTED TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATIVE.
 SHEET A-3 STILL INDICATES AN
 ALTERNATE SYSTEM, EVEN THOUGH DESIGN
 TEAM COMMENT SHEET INDICATES 2.5#
 GALVANIZED EXPANDED METAL DIAMOND MESH.
 SHEET S1OF 2 DETAIL SECTION1/S-1,
 INDICATES THE USE OF 1X FURRING AT 2'-0"
 O.C. SEE ASTM C1063 TABLE 3 TYPES AND
 WEIGHTS OF METAL PLASTER BASES AND
 CORRESPONDING MAXIMUM PERMISSIBLE
 SPACING OF SUPPORTS.CEILINGS, WOOD
 ASSEMBLIES ARE NOT TO SPAN MORE THAN 12"
 O.C.
  
 9)2ND REQUEST, FL BLD CODE 1609.6.2.1:
 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) PANEL WALLS- SOFFITS- PROROC
 EXTERIOR SOFFIT BOAARD.
 C) ROOFING ASSEMBLIES
  
 NOTE: WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 NOTE ROOFING NOA, SYSTEMS LIMITATIONS VS
 ENHANCED FASTENING!!!!!
  
 10) 2ND REQUEST, PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER
 OCTOBER 1, 2003 ARE REQUIRED TO COMPLY
 WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 16) 2ND REQUEST,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026