2006-06-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06051007
 ADD: 2001 PALM BCH LAKES BLVD.
 CONT: RIZNICK CONSTRUCTION
 TEL: ( )584-0363
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) MISSING SOILS REPORT,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE
 SOIL IS IN DOUBT, OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH
 1802.6 .
  
 3) S2-2: STRUCTURAL DESIGN CRITERIA,
 3A) THE PLANS STATE THEY ARE DESIGNED
 UNDER FBC 2001, PERMIT APPLICATIONS
 SUBMITTED AFTER SEPT30, 2005 REQUIRED
 DESIGN TO BE THE 2004 FLORIDA BUILDING
 CODE.
  
 3B) WIND DESIGN CRITERIA, DESIGN TO BE
 UNDER THE ASCE 7-02 SEE REFRENCE
 STANDARD CHAPTER 35.
  
 3C) MISSING MINIMUM BUILDINGDESIGN
 CRITERIA,110.2* W. P. B.
 ADMINISTRATIVE CODE, INFORMATION THAT IS
 REQUIRED FOR RECORD KEEPING & FOR
 CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) FLOOD ZONE
 H) FLOOD ELEVATION
 I)L.O.M.R.
  
 3D) MISSING THE WIND DESIGN INTERNAL
 PRESSURE COEFFICIENT WHEN DESIGNED TO
 ASCE 7-02. 1603.1.4(4) THE APPLICABLE
 ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE
 COEFFICIENT.
  
 4) PROVIDE ADDITIONAL INFORMATION,
 PERMIT APPLICATION PROJECT DESCRIPTION,
 IS ONLY FOR DRIVE THROUGH AND NOT
 LANDSCAPING, REPAVING OR CURBING OR
 STRIPING OF THE CURRENT SITE? IF SO
 INCLUDE UNDER PERMIT DESCPTION.
  
 5) PROVIDE CUT SECTION THROUGH DRIVE
 THROUGH INDICATING COMPLIANCE WITH AN
 ACCISSIBLE ATM AND NEW ROMOTE TELLAR
 STATIONS.11-4.2/ 11-7.2(2).
  
 6) A-2/ A-3 BOTH INDICATE THE USE OF (2)
 SCUPPERS ON THE EAST AND WEST
 ELEVATIONS, PLANS DO NOT INDICATE
 OVERFLOW SCUPPERS. 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW
 WATER IS NOT PROVIDED, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS OR PARAPETS NOT
 LESS THAN 2 INCHES (51 MM) NOR MORE THAN
 4 INCHES (102 MM) ABOVE THE FINISHED
 ROOF COVERING AND SHALL BE LOCATED AS
 CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS. AN OVERFLOW SCUPPER
 SHALL BE SIZED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, PLUMBING.
  
 7) A-2/ A-3 BOTH INDICATE THE USE OF
 SCUPPERS.1503.6 PROTECTION AGAINST DECAY
 AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS
 SHALL DISCHARGE AT LEAST 1 FOOT (305 MM)
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL
 EXTENSIONS, OR SPLASH BLOCKS. GUTTERS
 WITH DOWNSPOUTS ARE REQUIRED ON ALL
 BUILDINGS WITH EAVES OF LESS THAN 6
 INCHES (152 MM) HORIZONTAL PROJECTION
 EXCEPT FOR GABLE END RAKES OR ON A ROOF
 ABOVE ANOTHER ROOF.
  
 8) SHEET A-3 NOTE FOR USE OF ALTERNATE
 MATERIALS FOR CEILING APPLICATION.
 PROVIDE ADDTIONAL INFORMAATION ON THE
 TYPE OF WIRE LATH TO BE USED?
 2510.3INSTALLATION OF THESE MATERIALS
 SHALL BE IN COMPLIANCE WITH ASTM C 926
 AND ASTM C 1063.
 RULE 9B-72 PRODUCT APPROVAL FOR "PROROC
 EXTERIOR SOFFIT BOARD W/ FLORIDA STATE
 APPROVAL.
 ) 104.1.1* ALTERNATE MATERIALS, DESIGN
 & METHODS OF CONSTRUCTION & EQUIPMENT.
 THE PROVISIONS OF THIS CODE ARE NOT
 INTENDED TO PREVENT THE INSTALLATION OF
 ANY MATERIAL OR TO PROHIBIT ANY DESIGN
 OR METHOD OF CONSTRUCTION NOT
 SPECIFICALLY PRESCRIBED BY THIS CODE,
 PROVIDED THAT ANY SUCH ALTERNATIVE HAS
 BEEN APPROVED. AN ALTERNATE MATERIAL,
 DESIGN OR METHOD OF CONSTRUCTION SHALL
 BE APPROVED WHERE THE BUILDING OFFICIAL
 FINDS THAT THE PROPOSED DESIGN IS
 SATISFACTORY AND COMPLIES WITH THE
 INTENT OF THE PROVISIONS OF THIS CODE,
 AND THAT THE MATERIAL, METHOD OR WORK
 OFFERED IS, FOR THE PURPOSE INTENDED, AT
 LEAST THE EQUIVALENT OF THAT PRESCRIBED
 IN THIS CODE IN QUANITY, STRENGTH,
 EFFECTIVENESS FIRE RESISTANCE,
 DURABILITY AND SAFETY. WHEN ALTERNATE
 LIFE SAFETY SYSTEMS ARE DESIGNED, THE
 SFPE ENGINEERING GUIDE TO
 PERFORMANCE-BASED FIRE PROTECTION
 ANALYSIS AND DESIGN OF BUILDINGS , OR
 OTHER METHODS APPROVED BY THE BUILDING
 OFFICIAL MAY BE USED. THE BUILDING
 OFFICIAL SHALL REQUIRE THAT SUFFICIENT
 EVIDENCE OR PROOF BE SUBMITTED TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATIVE.
  
 9) FL BLD CODE 1609.6.2.1: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) PANEL WALLS- SOFFITS- PROROC
 EXTERIOR SOFFIT BOAARD.
 C) ROOFING ASSEMBLIES
  
 NOTE: WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 NOTE ROOFING NOA, SYSTEMS LIMITATIONS VS
 ENHANCED FASTENING!!!!!
  
 10)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) A3 PLANS DO NOT INDICATE TERMITE
 TREATMENT OF SLAB.
 1816.1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY
 REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER
 APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE
 SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF
 THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE
 ISSUED TO THE BUILDING DEPARTMENT BY THE
 LICENSED PEST CONTROL COMPANY THAT
 CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF
 SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 12) VENTING:1203.2 ATTIC SPACES.
 ENCLOSED ATTICS AND ENCLOSED RAFTER
 SPACES FORMED WHERE CEILINGS ARE APPLIED
 DIRECTLY TO THE UNDERSIDE OF ROOF
 FRAMING MEMBERS SHALL HAVE CROSS
 VENTILATION FOR EACH SEPARATE SPACE BY
 VENTILATING OPENINGS PROTECTED AGAINST
 THE ENTRANCE OF RAIN. BLOCKING AND
 BRIDGING SHALL BE ARRANGED SO AS NOT TO
 INTERFERE WITH THE MOVEMENT OF AIR. A
 MINIMUM OF 1 INCH (25 MM) OF AIRSPACE
 SHALL BE PROVIDED BETWEEN THE INSULATION
 AND THE ROOF SHEATHING. THE NET FREE
 VENTILATING AREA SHALL NOT BE LESS THAN
 1 / 150 OF THE AREA OF THE SPACE
 VENTILATED, WITH 50 PERCENT OF THE
 REQUIRED VENTILATING AREA PROVIDED BY
 VENTILATORS LOCATED IN THE UPPER PORTION
 OF THE SPACE TO BE VENTILATED AT LEAST 3
 FEET (914 MM) ABOVE EAVE OR CORNICE
 VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE
 VENTS.
  
 13)STRUCTURAL SHEETS: SEALED BY
 ARCHITECT, IF CONSULTING ENGINEER
 DESIGNED THIS STRUCTURE, PLANS SHOULD BE
 SEALED BY ENGINEER.FL S. S. 471,
 OTHERWISE WHY IS HIS TITLEBLOCK ON THIS
 SHEET.
  
 14) ARCHITECTS TITLE BLOCK:
 ) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 15) ARCHITECTURAL & STRUCTURAL SHEETS:
 ARCHITECT BUSINESS: OXIOS ARCHITECTS,
 P.A. ON SOME SHEETS USES THE FIRMS
 LICENSE NUMBER ON OTHER SHEETSOVIDIO
 OXIOS LICENSE NUMBER, NOT THE FIRMS
 LICENSE NUMBER. ) 481.219 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF
 AN ARCHITECT PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 16) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715