Plan Review Notes
Plan Review Notes For Permit 06050945
Permit Number 06050945
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-14 00:00:00******** UNSAT *********
  
 1) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52.
  
 2) NOTE: PLEASE SEE MISSING DEDICATED
 BATH CIRCUIT AND GFI PER
 210.52D,210.8A,210.11C3
  
 3) NOTE: PLEASE SEE MISSING EGRESS LT
 CONTROL AND FIXTURE PER 210.70, LS 101
 7.8.
  
 4) NOTE: PLEASE SEE AHU OCP TO BE A MIN
 OF 125%.
 424.3B
  
 5) NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT CIRCUITS.
 PLEASE SEE NOTE ON PLANS MENTIONS
 RECEPTS TO BE PROTECTED, HOWEVER PLEASE
 KNOW, THIS WAS THE PREVIOUS CODE AND
 PLEASE SEE 210.12B 2002 NEC.
  
 6) NOTE: PLEASE SPECIFY THE 2002 NEC ON
 PLANS.
 106.1.2
  
 7) NOTE: PLEASE SEE MISSING TWO SMALL
 APPLIANCE CIRCUITS ON PANEL SCHEDULE.
 THIS MAY BE SHOWN, HOWEVER PLEASE SEE
 THESE ARE BEING SHOWN AS 220V ON 2-POLE
 BRKR.
 210.52,210.11,220.16
  
 8) NOTE: PLEASE SPECIFIC CIRCUITS SHOULD
 BE INDICATE ON PANEL SCHEDULE FOR NEW
 CIRCUITS.
 408.4
 IE LIV RM LTS, BATH LTS ETC.
  
 9) NOTE: PLEASE KNOW, THE NEW FOOTER
 STEEL SHALL BE CONNECTED TO THE EXISTING
 GROUNDIGN ELECTRODE SYSTEM.'
 250.50
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]