| 2006-06-14 00:00:00 | ******** UNSAT ********* |
| | |
| | 1) NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52. |
| | |
| | 2) NOTE: PLEASE SEE MISSING DEDICATED |
| | BATH CIRCUIT AND GFI PER |
| | 210.52D,210.8A,210.11C3 |
| | |
| | 3) NOTE: PLEASE SEE MISSING EGRESS LT |
| | CONTROL AND FIXTURE PER 210.70, LS 101 |
| | 7.8. |
| | |
| | 4) NOTE: PLEASE SEE AHU OCP TO BE A MIN |
| | OF 125%. |
| | 424.3B |
| | |
| | 5) NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT CIRCUITS. |
| | PLEASE SEE NOTE ON PLANS MENTIONS |
| | RECEPTS TO BE PROTECTED, HOWEVER PLEASE |
| | KNOW, THIS WAS THE PREVIOUS CODE AND |
| | PLEASE SEE 210.12B 2002 NEC. |
| | |
| | 6) NOTE: PLEASE SPECIFY THE 2002 NEC ON |
| | PLANS. |
| | 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE MISSING TWO SMALL |
| | APPLIANCE CIRCUITS ON PANEL SCHEDULE. |
| | THIS MAY BE SHOWN, HOWEVER PLEASE SEE |
| | THESE ARE BEING SHOWN AS 220V ON 2-POLE |
| | BRKR. |
| | 210.52,210.11,220.16 |
| | |
| | 8) NOTE: PLEASE SPECIFIC CIRCUITS SHOULD |
| | BE INDICATE ON PANEL SCHEDULE FOR NEW |
| | CIRCUITS. |
| | 408.4 |
| | IE LIV RM LTS, BATH LTS ETC. |
| | |
| | 9) NOTE: PLEASE KNOW, THE NEW FOOTER |
| | STEEL SHALL BE CONNECTED TO THE EXISTING |
| | GROUNDIGN ELECTRODE SYSTEM.' |
| | 250.50 |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |