| Plan Review Notes For Permit 06050940 |
| Permit Number |
06050940 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-30 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT. | | | | | | 2) JOB ADDRESS NEEDS TO APPEAR ON PLANS. | | | | | | 3) PLEASE PROVIDE COMBUSTION AIR FOR GAS | | | CLOTHES DRYER, (OR IS IT A DIRECT VENT | | | DRYER IF SO STATE THIS ON PLANS). | | | | | | 4) AHU #1, TWO 10" RETURN AIR DUCTS DO | | | NOT ALLOW ENOUGH RETURN AIR FOR A 3.5 | | | TON A/C SYSTEM, PLEASE CORRECT. | | | | | | 5)CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY. PER 2004 FBC 106.1.1 | | | . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|