| Plan Review Notes For Permit 06050918 |
| Permit Number |
06050918 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-08 00:00:00 | | | | PROVIDE A FLOOR PLAN WITH THE FOLLOWING. | | | | | | 1} PROVIDE PLANS LOCATING THE UNITS | | | BEING INSTALLED. | | | | | | 2} SHOW FEEDER SIZES AND OCP. | | | | | | 3} SHOW THE DISCONNECT LOCATIONS PER | | | 440.14. | | | | | | 4} LOCATE THE REQUIRED RECEPTACLES PER | | | 210.63. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | |
|