| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | THE PERSON TAKING RESPONSIBILITY FOR THE |
| | DESIGN MUST PRINT AND SIGN THEIR NAME TO |
| | SAME PER 106.3.4.2. FBC AS AMENDED. THIS |
| | ARTICLE ALSO IS AN EXTRACTION FROM THE |
| | EXEMPTION IN CHAPTER 471 OF THE FLORIDA |
| | STATUTES , 471.003, ALLOWING YOU TO DRAW |
| | YOUR OWN PLANS . |
| | |
| | AS PER INSTRUCTION FROM THE BUILDING |
| | OFFICIAL, THIS DEPARTMENT REQUIRES ALL |
| | PLANS MUST CONTAIN THE PRINTED NAME AND |
| | SIGNATURE OF THE DESIGNER OF RECORD AS |
| | THE STATUTE INTENDS. PLEASE COMPLY WITH |
| | THIS STATUTE ON ALL DOCUMENTS DRAWN BY |
| | YOU AND SUBMITTED FOR REVIEW. |
| | |
| | PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT.THIS IS ALSO A |
| | REQUIREMENT OF THIS DEPARTMENT. |
| | |
| | THE LOAD CALCULATION MUST BE PER 220, |
| | PART II, OR 220.31(B), FOR EXISTING |
| | DWELLINGS. |
| | PLEASE RECALCULATE AND INDICATE WHICH |
| | ARTICLE IS BEING APPLIED. |
| | |
| | |
| | THE CODE REFERENCE ?NEC 384? IS FROM THE |
| | 1996 CODE. PLEASE UPDATE CODE SECTIONS |
| | IF USING THEM AS REFERENCE.ALSO THE |
| | REFERENCES TO THE 1999 CODE ARE NOT |
| | COMPLIANT. |
| | |