| Plan Review Notes For Permit 06050911 |
| Permit Number |
06050911 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-08-03 00:00:00 | | | | | | | DENIED | | | | | | 1) STRUCTURAL MULLION DESIGN REQUIRES | | | MORE INFORMATION. | | | A) HOW PLATE IS CONNECTED TO POST (NO | | | WELD SPECIFIED) | | | B) NO ELEVATION DETAIL, SHOW WHERE THE | | | MULLION IS ATTACHED TOP AND BOTTOM AND | | | THE STRUCTURE TO WHICH IT IS ATTACHED | | | C) PROVIDE WIND DESIGN CRITERIA PER | | | 1603.1.4 FBC | | | D) PROVIDE INFORMATION THAT DESIGN WILL | | | MEET ALL LOAD CONDITIONS AND IS | | | COMPATIBLE WITH A CURRENT STORE FRONT | | | PRODUCT APPROVAL | | | E) ENGINEER'S STAMP AND SIGNATURE IS ON | | | THE BACK OF THE DRAWING | | | | | | ****NOTE DUE TO THE MANY DEFICIENCIES | | | ONE COPY OF THIS DRAWING HAS BEEN | | | RETAINED AND WILL BE FORWARDED TO THE | | | FLORIDA BOARD OF PROFSIONAL ENGINEERS*** | | | | | | 2) PROVIDE STORE FRONT PRODUCT APPROVALS | | | PLEASE BE SURE THAT THEY ARE LARGE | | | MISSLE RATED (SOME ARE ONLY SMALL MISSLE | | | RATED FOR USE ABOVE 30 FT) | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|