2006-07-15 00:00:00******* PROVISO/ REVISION *********
  
 1) NOTE: PLEASE SEE THE SD'S IN THE
 EXISTING DWELLING INSIDE AND OUTSIDE ALL
 BEDRMS SHALL BE SHOWN ON A LAYOUT OF
 FLOOR PLAN SHOWING EITHER ALL NEW OR
 EXISTING MEETING THE CURRENT NFPA-72
 11.5.1.1. R-313
 PLANS MAY NOT QUOTE REQUIREMENTSIN
 LEIU OF SHOWING THE DETAILS.
  
 2) NOTE: PLEASE SEE GEN/LTS AND RECEPTS
 ARE STILL SHOWING VA'S OVER THE MAX
 PERMITTED. THIS WAS NOTED ON PREVIOUS
 REVIEW. PLEASE KNOW, MAX OF 1440VA IS
 PERMITTED. NOTE #4 PREVIOUS REVIEW.
  
 3) NOTE: PLEASE SEE ALL RECEPTS WITHIN
 6' OF WETBAR SINKS SHALL BE GFI/ GFI
 PROTECTED.
 210.8A7, PLEASE INDICATE THESE AS GFI.
  
 ** PLEASE KNOW, THE ABOVE SHALL BE
 REVISED SNA SUBMITTED ALONG WITH ANY
 OTHER REVISIONS BEFORE THE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 ** PLANS REVIEWED AND STAMPED BY THIS
 DEPT SHALL BE ON THE JOBSITE FOR
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  