| 2006-07-15 00:00:00 | ******* PROVISO/ REVISION ********* | | | | | | 1) NOTE: PLEASE SEE THE SD'S IN THE | | | EXISTING DWELLING INSIDE AND OUTSIDE ALL | | | BEDRMS SHALL BE SHOWN ON A LAYOUT OF | | | FLOOR PLAN SHOWING EITHER ALL NEW OR | | | EXISTING MEETING THE CURRENT NFPA-72 | | | 11.5.1.1. R-313 | | | PLANS MAY NOT QUOTE REQUIREMENTSIN | | | LEIU OF SHOWING THE DETAILS. | | | | | | 2) NOTE: PLEASE SEE GEN/LTS AND RECEPTS | | | ARE STILL SHOWING VA'S OVER THE MAX | | | PERMITTED. THIS WAS NOTED ON PREVIOUS | | | REVIEW. PLEASE KNOW, MAX OF 1440VA IS | | | PERMITTED. NOTE #4 PREVIOUS REVIEW. | | | | | | 3) NOTE: PLEASE SEE ALL RECEPTS WITHIN | | | 6' OF WETBAR SINKS SHALL BE GFI/ GFI | | | PROTECTED. | | | 210.8A7, PLEASE INDICATE THESE AS GFI. | | | | | | ** PLEASE KNOW, THE ABOVE SHALL BE | | | REVISED SNA SUBMITTED ALONG WITH ANY | | | OTHER REVISIONS BEFORE THE ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. | | | ** PLANS REVIEWED AND STAMPED BY THIS | | | DEPT SHALL BE ON THE JOBSITE FOR | | | INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|