| 2006-06-13 00:00:00 | ****** UNSAT ***** |
| | |
| | 1) NOTE: PLEASE SEE ZONING NOTES AS |
| | FRONT COVER SHEETS ARE COLORED |
| | PHOTO-COPIES OF OLDER SURVEYS FOR OTHER |
| | WORK. |
| | |
| | 2) NOTE: PLEASE SEE FBC 2004 R 313 WHICH |
| | REQUIRES SD'S IN NEWAND EXISTING. |
| | PLEASE INDICATE EITHER EXISTING SD'S |
| | WHICH MEET CURRENT CODES IN EXISTING |
| | DWELLING AREAS, OR SHOW NEW SD'S. |
| | NFPA-72 11.5.1.1, 11.8.3.5 |
| | |
| | 3) NOTE: PLEASE SEE PANEL SCHEDULE SAHLL |
| | INDICATE THE CIRCUITS TO THE SPECIFIC |
| | NEW AREAS. 408.4 |
| | IE; BATH RECEPT, LIV AREA LTS, ETC |
| | |
| | 4) NOTE: PLEASE CLARIFYLT CIRCUIT, SA |
| | THE MAX VA ON A 15AMP CIRCUIT IS 1440 |
| | VA, AND PANEL SCHEDULE SHOWS 2200 |
| | PLEASE ADJUST. |
| | |
| | 5) NOTE: PLEASE SEE MISSING FOOTER STEEL |
| | AS PART OF THE GROUNDING ELECTRODE |
| | SYSTEM. THIS IS NEW FOOTER STEEL. |
| | 250.50 |
| | |
| | 6) NOTE: PLEASE CORRELATE RISER AND |
| | PLANS. PLEASE SEE RISER SHOWS A MAIN |
| | DISCONNECT, YET PLANS DO NOT INDICATE |
| | THIS? |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE PANEL INSIDE DOES |
| | NOT MEET 110.26 FOR MIN CLEARENCES. |
| | PLEASE RELOCATE. |
| | |
| | 8) NOTE: PLEASE VERIFY THE KW SHOWN FOR |
| | THE EXISTING RANGE AS 15KW EXCEEDS THE |
| | RATING OF THE 50A BRKR BY 12.5AMPS. |
| | PLEASE SEE 240.4,310.16,422.11 |
| | |
| | 9) NOTE: PLEASE SEE WASHER AND DRYER ARE |
| | BEING SHOWN BEING FED FROM EXISTING |
| | PANEL, HOWEVER THIS IS THE NEW PANEL? |
| | PLEASE PROVIDE A PANEL SCHEDULE FOR ALL |
| | AS IT SEEMS THE NEW PANEL BEING PROPOSED |
| | WILL FEED THE NEW AND EXISTING |
| | CIRCUITING. |
| | 408.4,215.5 |
| | |
| | 10) NOTE: PLEASE SEE SOME NOTES ON LEFT |
| | WHICH DO NOT SEEM TO APPLY. |
| | PLEASE SEE NOTE WHICH MENTIONS ALL |
| | BRNACH CIRCUITS BRKRS SHALL HAVE SURGE |
| | PROTECTION? |
| | PLEASE SEE NOTE FOR LANDSCAPE LTS? |
| | |
| | 11) NOTE: PLEASE SEE PLANS SHALL |
| | INDICATE THE FOLLOWING CURRENT CODES AT |
| | A MIN FOR ELECTRICAL REVIEW. |
| | FBC 2004, NFPA-72 2002, NFPA-70 2002 |
| | |
| | 12) NOTE: PLEASE SEE BUILDING REVIEW |
| | COMMENTS AS VALUE SHALL BE ADJUSTED PER |
| | FBC 2004 108.3 ADMINISTRATIVE SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |