Plan Review Notes
Plan Review Notes For Permit 06050902
Permit Number 06050902
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
  
 _XX_1.)A NOTICE OF COMMENCEMENT
 MUST BE FILED WITH THE CLERK OF COURTS
 BEFORE A PERMIT CAN BE ISSUED.
  
 _XX_2.)CONTRACTOR IS TO PROVIDE THE
 MEAN ROOF HEIGHT ON THE APPLICATION.
 MEAN ROOF HEIGHT FBC1609.2 IS DEFINED AS
 "THE AVERAGE OF THE ROOF EAVE HEIGHT AND
 THE HEIGHT TO THE HIGHTEST POINT ON THE
 ROOF SURFACE . . . "THE STATED MRH OF
 9' IS NOT CORRECT, PLEASE REVISE.IF IT
 IS LESS THAN 30', YOU MAY PROVIDE "<30'"
 RATHER THAN THE EXACT HEIGHT.
  
 _XX_3.)CONTRACTOR IS TO PROVIDE THE
 ROOF PITCH ON THE APPLICATION.
  
 _XX_4.)CONTRACTOR IS TO PROVIDE THE
 ROOF DECK TYPE ON THE APPLICATION.
  
 _XX_5.)FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO
 THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
 I HAVE PRINTED THIS FOR YOU; PLEASE
 RETAIN IN THE PACKAGE.
  
 ____6.)FOR THE FLAT DECK, SELECT THE
 APPROVED ASSEMBLY YOU ARE USING.
  
 ____7.)THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ____.
  
 ____8.)THE SYSTEM PROVIDED STATES
 LIMITATION #9, ENHANCED FASTENING NOT
 ALLOWED.
  
 ____9.)PROVIDE AN ENGINEER?S LETTER
 TO CONFIRM THAT THE ROOF WHICH CURRENTLY
 HAS SHINGLES INSTALLED CAN ACCOMMODATE
 THE ADDITIONAL WEIGHT OF THE PROPOSED
 TILE.
  
 ____ 10.)ON THE TILE PRODUCT APPROVAL,
 INDICATE WHICH METHOD OF ATTACHMENT YOU
 ARE USING.
  
 _XX_ 11.)THE PERMIT APPLICATION STATES
 THAT THIS IS A ROOF OVER.THIS IS NOT
 INCLUDED IN THE PAPERWORK PROVIDED. THE
 APPLICATION IS TO CLEARLY STATE THE
 SCOPE OF WORK. IF YOU PROVIDE A STATE OR
 LOCAL PRODUCT APPROVAL WHICH IS FOR A
 ROOF OVER, REVISE THE PERMIT APPLICATION
 TO STATE WHAT THE EXISTING ROOF COVERING
 IS.
  
 _XX_ 12.)THE HOUSE ELEVATIONS PROVIDED
 ARE NOT REQUIRED.HOWEVER, IF YOU WISH
 FOR THIS TO BE A PART OF THE PERMIT
 PACKAGE, DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FAC61G15-23.002.
  
 _XX_13.)IT APPEARS THAT THERE ARE
 TWO DIFFERENT ROOF PITCH AREAS, ONE FOR
 THE HIP, ONE FOR THE GABLE AREA.
 PROVIDE BOTH.
  
 _XX_ 14.)WITHOUT THE EXISTING ROOF
 PITCH, CODE COMPLIANCE CANNOT BE
 DETERMINED.IT APPEARS THAT ENGINEERING
 WILL BE REQUIRED FOR ENHANCED FASTENING
 FOR ZONES 2 AND 3.THE SYSTEM HAS A
 DESIGN PRESSURE LIMITATION OF -52.5.
 SEE ATTACHED FBC TABLE 1609.6B.
  