Plan Review Notes
Plan Review Notes For Permit 06050897
Permit Number 06050897
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-24 00:00:00 
  
 1} OUR RECORDS INDICATE AN APARTMENT ON
 THE PROPERTY. PLEASE SUBMIT LOAD
 CALCULATIONS FOR THE RESIDENCE PER
 220.30 OR 220. PART II.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  