| 2006-05-24 00:00:00 | | | | | | | 1} OUR RECORDS INDICATE AN APARTMENT ON | | | THE PROPERTY. PLEASE SUBMIT LOAD | | | CALCULATIONS FOR THE RESIDENCE PER | | | 220.30 OR 220. PART II. | | | | | | 2} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR | | | THE DESIGN MUST PRINT AND SIGN THEIR | | | NAME TO SAME PER 106.3.4.2. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|