| 2006-08-16 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | 3RD REVIEW, FROM PREVIOUS LIST: |
| | |
| | _XX_2.PROVIDE BUILDING HEIGHT ON THE |
| | PLAN.DESIGN PRESSURES FOR BUILDINGS |
| | OVER 60FEET ARE REQUIRED TO BE DESIGNED |
| | USING ASCE7, FBC1609.1.1 AND MUST BE |
| | DONE BY AN ENGINEER. DOCUMENTS PREPARED |
| | BY AN ENGINEER AND SUBMITTED FOR PUBLIC |
| | RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| | FAC61G15-23.002. |
| | |
| | 2ND REVIEW - PAPERWORK SUBMITTED SHOWS A |
| | MEAN ROOF HEIGHT OF 120'. |
| | |
| | 3RD REVIEW - ENGINEERING REQUIRED. |
| | |
| | _XX_4.ANCHORING NOT COMPLIANT FOR |
| | THE DESIGN PRESSURES YOU HAVE DECLARED. |
| | |
| | 3RD REVIEW - YOU HAVE CIRCLED ANCHORING |
| | FOR -60PSF, THE COMPUTERIZED ENGINEERING |
| | SPECIFIES -108.6. |
| | |
| | DESIGN PRESSURES FOR BUILDINGS OVER 60' |
| | MUST BE SPECIFIED BY AN ENGINEER.TWO |
| | SIGNED, SEALED, DATED ORIGINALS |
| | REQUIRED.YOU CANNOT USE A COMPUTER |
| | PROGRAM TO DETERMINE DESIGN PRESSURES |
| | FOR BUILDINGS OVER 60' UNLESS IT IS |
| | SEALED BY AN ENGINEER. |
| | |