| 2006-09-29 00:00:00 | ******REVISION DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR GAS PLAN REVIEW ON THE SUBMITTED |
| | REVISION: |
| | |
| | 1. SUBMIT TWO COPIES OF A SITE SURVEY |
| | PLAN INDICATING THE NEW PROPOSED |
| | LOCATION OF THE GENERATOR WITH THE |
| | INDICATION OF ALL DIMENSIONS FROM |
| | PROPERTY LINES AND DISTANCES FROM |
| | ADJACENT STRUCTURES. |
| | 2. INDICATE ON THE SITE SURVEY PLAN THAT |
| | THE NEW LOCATION GENERATOR EXHAUST ARE |
| | NOT INSTALLED ANY CLOSER THAN TEN FEET |
| | FROM ANY OPENING INTO THE DWELLING |
| | STRUCTURE. THIS INCLUDES DOORS, WINDOWS, |
| | AND ATTIC VENTILATION OPENINGS. |
| | 3. SUBMIT TWO COPIES OF MANUFACTURER |
| | INSTALLATION INSTRUCTIONS AND |
| | MANUFAFTURER SPECIFICATIONS INDICATING |
| | GENERATOR DIMENTIONS, BTU LOAD AND |
| | INSTALLATIONCLEARENCES FROM ADJACENT |
| | STRUCTURES. |
| | 4. THE APPROVED GENERATOR FOR SAID |
| | ADDRESS IS A 37KW NATURAL GAS GENERATOR |
| | NOT A 38KW PLEASE CORRECT FOR |
| | RESUBMITTAL. |
| | 5. THE APPROVED GENERATOR BTU LOAD IS |
| | 570,000 NOT 623,000 PLEASE CORRECT FOR |
| | RESUBMITTAL. |
| | 6. THE TOTAL BTU'S ARE INCORRECT ON THE |
| | DRAWING. THE CORRECT TOTAL BTU'S SHOULD |
| | BE 1,292,000 NOT 1,345,OOO PLEASE |
| | CORRECT FOR RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |