| Plan Review Notes For Permit 06050858 |
| Permit Number |
06050858 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-08-21 00:00:00 | *** PROVISO *** | | | 1)SMOKE DETECTORS SHALL BE INSTALLED IN | | | A/C SUPPLY SYSTEMS WITH A DESIGN | | | CAPACITY GREATER THAN 2,000 CFM, IN THE | | | SUPPLY AIR DUCT. 2004 FBC(M) 606.2.1OR | | | UPON ACTIVATION, THE SMOKE DETECTORS | | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | | SYSTEM. 2004 FBC(M) 606.4 . | | | 2) AIR DAMPERS REQUIRED AT GRILLS THAT | | | DO NOT HAVE DUCT DAMPERS. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|