Plan Review Notes
Plan Review Notes For Permit 06050858
Permit Number 06050858
Review Stop M
Sequence Number 3
Notes
Date Text
2006-08-21 00:00:00*** PROVISO ***
 1)SMOKE DETECTORS SHALL BE INSTALLED IN
 A/C SUPPLY SYSTEMS WITH A DESIGN
 CAPACITY GREATER THAN 2,000 CFM, IN THE
 SUPPLY AIR DUCT. 2004 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2004 FBC(M) 606.4 .
 2) AIR DAMPERS REQUIRED AT GRILLS THAT
 DO NOT HAVE DUCT DAMPERS.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.